Honeywell NOTIFIER NFS-320C Manual Download Page 3

Canadian DN-60085:J • 12/20/2013 — Page 3 of 6

V

OICE

 F

EATURES

Integrates with FirstCommand Series. 

See DN-60772.

Note: Only NFC-50/100 and NFC-LOC are approved for
Canadian applications.

H

IGH

-

EFFICIENCY

 

OFFLINE

 

SWITCHING

 

3.0 A 

POWER

 

SUPPLY

 (6.0 A 

IN

 

ALARM

)

120  VAC.

Displays battery current/voltage on panel (with display).

FlashScan, Exclusive 
World-Leading Detector Protocol

At the heart of the NFS-320C is a set of detection devices and
device protocol — FlashScan (U.S. Patent 5,539,389). FlashS-
can is an all-digital protocol that gives superior precision and
high noise immunity.

In addition to providing quick identification of an active input
device, this protocol can also activate many output devices in a
fraction of the time required by competitive protocols. This high
speed also allows the NFS-320C to have the largest device per
loop capacity in the industry — 318 points — yet every input
and output device is sampled in less than two seconds. The
microprocessor-based FlashScan detectors have bicolor LEDs
that can be coded to provide diagnostic information, such as
device address during Walk Test.

ONYX Intelligent Sensing

Intelligent sensing is a set of software algorithms that provides
the NFS-320C with industry-leading smoke detection capabil-
ity. These complex algorithms require many calculations on
each reading of each detector, and are made possible by the
high-speed microcomputer used by the NFS-320C.

Drift Compensation and Smoothing:

 Drift compensation

allows the detector to retain its original ability to detect actual
smoke, and resist false alarms, even as dirt accumulates. It
reduces maintenance requirements by allowing the system to
automatically perform the periodic sensitivity measurements
required by NFPA 72. Smoothing filters are also provided by
software to remove transient noise signals, such as those
caused by electrical interference.

Maintenance Warnings:

 When the drift compensation per-

formed for a detector reaches a certain level, the performance
of the detector may be compromised, and special warnings
are given. There are three warning levels: (1) Low Chamber
value; (2) Maintenance Alert, indicative of dust accumulation
that is near but below the allowed limit; (3) Maintenance
Urgent, indicative of dust accumulation above the allowed limit.

Sensitivity Adjust:

 Nine sensitivity levels are provided for

alarm detection. These levels can be set manually, or can
change automatically between day and night. Nine levels of
pre-alarm sensitivity can also be selected, based on predeter-
mined levels of alarm. Pre-alarm operation can be latching or
self-restoring, and can be used to activate special control func-
tions.

Self-Optimizing Pre-Alarm

: Each detector may be set for

“Self-Optimizing” pre-alarm. In this special mode, the detector
“learns” its normal environment, measuring the peak analog
readings over a long period of time, and setting the pre-alarm
level just above these normal peaks.

Cooperating Multi-Detector Sensing:

 A patented feature of

ONYX intelligent sensing is the ability of a smoke sensor to
consider readings from nearby sensors in making alarm or
pre-alarm decisions. Without statistical sacrifice in the ability to
resist false alarms, it allows a sensor to increase its sensitivity
to actual smoke by a factor of almost two to one.

Field Programming Options

Autoprogram

 is a timesaving feature. The FACP “learns” what

devices are physically connected and automatically loads
them in the program with default values for all parameters.
Requiring less than one minute to run, this routine allows the
user to have almost immediate fire protection in a new installa-
tion, even if only a portion of the detectors are installed.

Keypad Program Edit (with KDM-R2) 

The NFS-320C, like all

NOTIFIER intelligent panels, has the exclusive feature of pro-
gram creation and editing capability from the front panel key-
pad, 

while continuing to provide fire protection

. The

architecture of the NFS-320C software is such that each point
entry carries its own program, including control-by-event links
to other points. This allows the program to be entered with
independent per-point segments, while the NFS-320C simulta-
neously monitors other (already installed) points for alarm con-
ditions.

VeriFire® Tools is an offline programming and test utility that
can greatly reduce installation programming time, and
increase confidence in the site-specific software. It is Win-
dows®-based and provides technologically advanced capabili-
ties to aid the installer. The installer may create the entire
program for the NFS-320C in the comfort of the office, test it,
store a backup file, then bring it to the site and download from
a laptop into the panel.

Placement of Equipment 
in Chassis and Cabinet

The following guidelines outline the NFS-320C’s flexible sys-
tem design.

Wiring:

 When designing the cabinet layout, consider separa-

tion of power-limited and non-power-limited wiring as dis-
cussed in the 

NFS-320/C/E Installation Manual

.

It is critical that all mounting holes of the NFS-320C are
secured with a screw or standoff to ensure continuity of Earth
Ground.

Networking:

 If networking two or more control panels, each

unit requires a Network Communication Module or High-
Speed Network Communication Module (HS-NCM can sup-
port two nodes; see “Networking Options” on page 5). These
modules can be installed in any option board position (see
manual), and additional option boards can be mounted in front
of them.

KDM-R2 Controls and Indicators

Program Keypad:

 QWERTY type (keyboard layout).

12 LED Indicators:

 Power; Fire Alarm; Pre-Alarm; Security;

Supervisory; System Trouble; Signals Silenced; Points Dis-
abled; Control Active; Abort; Pre-Discharge; Discharge.

Keypad Switch Controls:

 Acknowledge/Scroll Display; Signal

Silence; Drill; System Reset; Lamp Test.

LCD Display:

 80 characters (2 x 40) with long-life LED back-

light.

Summary of Contents for NOTIFIER NFS-320C

Page 1: ...pliance Circuits NAC Selectable System Sensor S or Gentex strobe synchronization Built in Alarm Trouble Security and Supervisory relays VeriFire Tools online or offline programming utility Upload Download save store check compare and simulate panel databases Upgrade panel firmware Autoprogramming and Walk Test reports Optional universal 318 point DACT 80 character remote annunciators up to 32 EIA ...

Page 2: ...Automatic drift compensation of smoke sensor and CO cell High nuisance alarm immunity FSA 8000A INTELLIGENT FAAST DETECTOR Connects directly to the SLC loop of compatible ONYX series panels Provides five event thresholds that can be individually pro grammed with descriptive labels for control by event pro gramming uses five detector addresses Uses patented particle separator and field replaceable ...

Page 3: ...ak analog readings over a long period of time and setting the pre alarm level just above these normal peaks Cooperating Multi Detector Sensing A patented feature of ONYX intelligent sensing is the ability of a smoke sensor to consider readings from nearby sensors in making alarm or pre alarm decisions Without statistical sacrifice in the ability to resist false alarms it allows a sensor to increas...

Page 4: ...or Active LED Trouble LED and switch per circuit Active Alarm LEDs can be programmed by powered up switch selection by point to be red green or yel low the Trouble LED is always yellow See DN 6862 AEM 24AT Same LED and switch capabilities as ACM 24AT expands the ACM 24AT to 48 72 or 96 points See DN 6862 ACM 48A ONYX Series ACS annunciator up to 96 points of annunciation with Alarm or Active LED p...

Page 5: ...3 SLC IM SLC integration module for VESDAnet detectors See DN 60755 NETWORKING OPTIONS NCM W NCM F Standard Network Communications Mod ules Wire and multi mode fiber versions available See DN 6861 HS NCM W MF SF WMF WSF MFSF High speed Network Communications Modules that can connect to two nodes Wire single mode fiber multi mode fiber and media conver sion models are available See DN 60454 RPT W R...

Page 6: ... cm depth When using trim ring TR 320 mount backbox with at least 1 inch 2 54 cm between wall surface and front of backbox to allow door to open fully past the trim ring The TR 320 molding width is 0 905 in 2 299 cm SHIPPING WEIGHT NFS 320C 37 lb 16 78 kg without batteries TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 49 C and at a relative humidity 93 2 RH...

Reviews: