DN-60085:J • 12/20/2013 — Page 1 of 6

NFS-320C

Intelligent Addressable
Fire Alarm System

Intelligent Fire Alarm Control Panels

Canadian DN-60085:J • A-15

General

The NFS-320C intelligent Fire Alarm Control Panel is part of
the ONYX® Series of Fire Alarm Controls from NOTIFIER.

In stand-alone or network configurations, ONYX Series prod-
ucts meet virtually every application requirement.

The NFS-320C’s modular design makes system planning eas-
ier. The panel can be configured with just a few devices for
small building applications, or networked with many devices to
protect a large campus or a high-rise office block. Simply add
additional peripheral equipment to suit the application. For
example, certain geographic regions such as Canada have
specific LED annunciation requirements. To provide up to 48
zones/points in the same cabinet, add an optional ACM Series
annunciator (sold separately). 

Features

Listed to Standard ULC-S527-99.

Certified for seismic applications when used with the appro-
priate seismic mounting kit. 

Approved for Marine applications when used with listed
compatible equipment. 

See DN-60688. 

One isolated intelligent Digital Communications Loop (DCL)
Style 4, 6 or 7.

Up to 159 detectors (any mix of ion, photo, thermal, or
multi-sensor) and 159 modules (Addressable pull station,
normally-open contact devices, two-wire smoke detectors,
notification, or relay). 318 devices maximum.

Standard 80-character display.

Network options:

High-speed network for up to 200 nodes (NFS2-3030,
NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM,
ONYXWorks, NFS-3030, NFS-640, and NCA).

Standard network for up to 103 nodes (NFS2-3030,
NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM,
ONYXWorks, NCS, NFS-3030, NFS-640, NCA, AFP-200,
AFP-300/400, AFP-1010, and AM2020). Up to 54 nodes
when DVC-EM is used in network paging.

6.0 A power supply with four Class A/B built-in Notification
Appliance Circuits (NAC). Selectable System Sensor, S, or
Gentex strobe synchronization.

Built-in Alarm, Trouble, Security, and Supervisory relays.

VeriFire® Tools online or offline programming utility. Upload/
Download, save, store, check, compare, and simulate panel
databases. Upgrade panel firmware.

Autoprogramming and Walk Test reports.

Optional universal 318-point DACT.

80-character remote annunciators (up to 32).

EIA-485 annunciators, including custom graphics.

Printer interface (80-column and 40-column printers).

History file with 800-event capacity in nonvolatile memory,
plus separate 200-event alarm-only file.

Alarm Verification selection per point, with automatic
counter.

Presignal/Positive Alarm Sequence (PAS).

Silence inhibit and Auto Silence timer options.

March time / temporal / Canadian two-stage coding, 20 ppm
and temporal / strobe synchronization.

Field-programmable on panel or on PC, with VeriFire Tools
program check, compare, simulate.

Full QWERTY keypad.

Battery charger supports 18 – 200 AH batteries. 

Non-alarm points for lower priority functions.

Remote ACK/Signal Silence/System Reset/Drill via monitor
modules.

Automatic time control functions, with holiday exceptions.

Surface Mount Technology (SMT) electronics.

Extensive, built-in transient protection.

Powerful Boolean logic equations.

F

LASH

S

CAN

® I

NTELLIGENT

 F

EATURES

Polls up to 318 devices in less than two seconds.

Activates up to 159 outputs in less than five seconds.

Multicolor LEDs blink device address during Walk Test.

Fully digital, high-precision protocol (U.S. Patent
5,539,389).

Manual sensitivity adjustment — up to nine levels (see indi-
vidual device information for available settings).

Pre-alarm ONYX intelligent sensing — up to nine levels.

Day/Night automatic sensitivity adjustment.

Sensitivity windows:

– Ion  – 

0.5 to 2.5%/foot obscuration.

– Photo – 

0.5 to 2.35%/foot obscuration.

– Laser (VIEW®) – 

0.02 to 2.0%/foot obscuration.

– Acclimate Plus™ – 

0.5 to 4.0%/foot obscuration.

– IntelliQuad –

 1.0 to 4.0%/foot obscuration.

– IntelliQuad™ PLUS – 

1.0 to 4.0%/foot obscuration

Drift compensation (U.S. Patent 5,764,142).

NFS-320C

6008

5c

o

v.

jpg

Summary of Contents for NOTIFIER NFS-320C

Page 1: ...pliance Circuits NAC Selectable System Sensor S or Gentex strobe synchronization Built in Alarm Trouble Security and Supervisory relays VeriFire Tools online or offline programming utility Upload Download save store check compare and simulate panel databases Upgrade panel firmware Autoprogramming and Walk Test reports Optional universal 318 point DACT 80 character remote annunciators up to 32 EIA ...

Page 2: ...Automatic drift compensation of smoke sensor and CO cell High nuisance alarm immunity FSA 8000A INTELLIGENT FAAST DETECTOR Connects directly to the SLC loop of compatible ONYX series panels Provides five event thresholds that can be individually pro grammed with descriptive labels for control by event pro gramming uses five detector addresses Uses patented particle separator and field replaceable ...

Page 3: ...ak analog readings over a long period of time and setting the pre alarm level just above these normal peaks Cooperating Multi Detector Sensing A patented feature of ONYX intelligent sensing is the ability of a smoke sensor to consider readings from nearby sensors in making alarm or pre alarm decisions Without statistical sacrifice in the ability to resist false alarms it allows a sensor to increas...

Page 4: ...or Active LED Trouble LED and switch per circuit Active Alarm LEDs can be programmed by powered up switch selection by point to be red green or yel low the Trouble LED is always yellow See DN 6862 AEM 24AT Same LED and switch capabilities as ACM 24AT expands the ACM 24AT to 48 72 or 96 points See DN 6862 ACM 48A ONYX Series ACS annunciator up to 96 points of annunciation with Alarm or Active LED p...

Page 5: ...3 SLC IM SLC integration module for VESDAnet detectors See DN 60755 NETWORKING OPTIONS NCM W NCM F Standard Network Communications Mod ules Wire and multi mode fiber versions available See DN 6861 HS NCM W MF SF WMF WSF MFSF High speed Network Communications Modules that can connect to two nodes Wire single mode fiber multi mode fiber and media conver sion models are available See DN 60454 RPT W R...

Page 6: ... cm depth When using trim ring TR 320 mount backbox with at least 1 inch 2 54 cm between wall surface and front of backbox to allow door to open fully past the trim ring The TR 320 molding width is 0 905 in 2 299 cm SHIPPING WEIGHT NFS 320C 37 lb 16 78 kg without batteries TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 49 C and at a relative humidity 93 2 RH...