Page 4 of 6 — Canadian DN-60085:J • 12/20/2013
Product Line Information
•
“Configuration Guidelines” on page 4
•
“Main System Components” on page 4
•
“Networking Options” on page 5
•
“Auxiliary Power Supplies and Batteries” on page 4
•
•
“Compatible Devices, EIA-232 Ports” on page 4
•
“Compatible Devices, EIA-485 Ports” on page 4
•
“Compatible Intelligent Devices” on page 4
•
“Enclosures, Chassis, and Dress Plates” on page 5
•
C
ONFIGURATION
G
UIDELINES
The NFS-320C system ships assembled; description and
some options follow. See “Enclosures, Chassis, and Dress
Plates” on page 5 for information about mounting peripherals.
NOTE:
Stand-alone and network systems require a main display.
On stand-alone systems, the panel’s keypad provides the required
display. On network systems (two or more networked fire panel
nodes), at least one NCA-2, NCS, or ONYXWorks annunciation
device is required. For NCA-2, see DN-7047.)
M
AIN
S
YSTEM
C
OMPONENTS
NFS-320C:
The standard, factory-assembled NFS-320C sys-
tem includes the following components: one control panel
mounted on chassis (120 V operation — ships with grounding
cable, battery interconnect cables, and document kit); one
integral power supply mounted to the control panel; one pri-
mary display KDM-R2 keypad/display; and one cabinet for sur-
face or semi-flush mounting.
Purchase batteries separately.
One or two option boards may be mounted to the NFS-320
cabinet, with one visible to the left of the display and one
inside; additional option boards can be used in remote cabi-
nets. See Canadian applications manual addendum 52747.
NFS-320CR:
Same as NFS-320C but in red enclosure.
NFS-320C-FR:
Same as NFS-320C but in French language.
TR-320:
Trim ring for the NFS-320C cabinet.
A
UXILIARY
P
OWER
S
UPPLIES
AND
B
ATTERIES
ACPS-610:
6.0 A or 10.0 A addressable charging power sup-
ply.
See DN-60244.
FCPS-24S6C/8C:
Remote 6 A and 8 A power supplies. See
DN-6297. For use only as a NAC expander.
BAT Series:
Batteries. NFS-320 uses two 12 volt, 18 to 200
AH batteries.
See DN-6933.
A
UDIO
O
PTIONS
NFC-50/100:
25 watt, 25 VRMS, emergency Voice Evacuation
Control Panel (VECP) with integral commercial microphone,
digital message generator, and Class A or Class B speaker cir-
cuits.
See DN-60772.
C
OMPATIBLE
D
EVICES
, EIA-232 P
ORTS
PRN-6:
80-column printer.
See DN-6956.
VS4095/5:
Keltron printer, 40-column, 24 V. Mounted in exter-
nal backbox.
See DN-3260.
(Not ULC-listed.)
DPI-232:
Direct Panel Interface, specialized modem for
extending serial data links to remotely located FACPs and/or
peripherals; mount on NFS-320 chassis.
See DN-6870.
C
OMPATIBLE
D
EVICES
, EIA-485 P
ORTS
ACM-24AT:
ONYX Series ACS annunciator – up to 96 points
of annunciation with Alarm or Active LED, Trouble LED, and
switch per circuit. Active/Alarm LEDs can be programmed (by
powered-up switch selection) by point to be red, green, or yel-
low; the Trouble LED is always yellow.
See DN-6862.
AEM-24AT:
Same LED and switch capabilities as ACM-24AT,
expands the ACM-24AT to 48, 72, or 96 points.
See DN-6862.
ACM-48A:
ONYX Series ACS annunciator – up to 96 points of
annunciation with Alarm or Active LED per circuit. Active/
Alarm LEDs can be programmed (by powered-up switch selec-
tion) in groups of 24 to be red, green, or yellow. Expandable to
96 points with one AEM-48A.
See DN-6862.
AEM-48A:
Same LED capabilities as ACM-48A, expands the
ACM-48A to 96 points.
See DN-6862.
ACM-8R:
Remote Relay Module with eight Form-C contacts.
Can be located up to 6,000 ft. (1828.8 m) from panel on four
wires.
See DN-3558.
LCD-80: ACS mode.
80-character, backlit LCD display.
Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32 per
FACP.
See LCD-80/LCD-80TM (DN-3198).
FDU-80:
Terminal mode. 80-character, backlit LCD display.
Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32 per
FACP. Not for use as a primary display in Canada.
See FDU-
80 (DN-6820).
LCD2-80:
Terminal and ACS mode. 80-character, backlit LCD
display. Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32
per FACP. Not for use as primary display in Canadian applica-
tions.
See DN-60548.
LDM:
Lamp Driver Modules LDM-32, LDM-E32, and LDM-
R32; remote custom driver modules.
See DN-0551.
SCS:
Smoke control stations SCS-8, SCE-8, with lamp drivers
SCS-8L, SCE-8L; eight (expandable to 16) circuits (HVAC
only).
See DN-4818.
TM-4:
Transmitter Module. Includes three reverse-polarity cir-
cuits and one municipal box circuit; mount on NFS-320C chas-
sis or remotely.
See DN-6860.
UDACT-2:
Universal Digital Alarm Communicator Transmitter,
636 channel.
See DN-60686.
UZC-256:
Programmable Universal Zone Coder provides pos-
itive non-interfering successive zone coding. Microprocessor-
controlled, field-programmable from IBM®-compatible PCs
(requires optional programming kit). Mounts in BB-UZC or
other compatible chassis (purchased separately).
See DN-
3404.
C
OMPATIBLE
I
NTELLIGENT
D
EVICES
FSA-8000A:
Intelligent FAAST Fire Alarm Aspiration Sensing
Technology®. Intelligent aspirating smoke detector with ULC
listing.
See DN-60792.
FSB-200A:
Intelligent beam smoke detector.
See DN-6985.
FSB-200SA:
Intelligent beam smoke detector with integral
sensitivity test.
See DN-6895.
FSC-851A:
FlashScan IntelliQuad Advanced Multi-Criteria
Detector.
See DN-60412.
FCO-851A:
FlashScan IntelliQuad PLUS Advanced Multi-Cri-
teria Fire/CO Detector.
See DN-60689.
FSI-851A:
Low-profile FlashScan ionization detector.
See DN-
6934.
FSP-851A:
Low-profile FlashScan photoelectric detector.
See
DN-6935.
FSP-851TA:
Low-profile FlashScan photoelectric detector with
135°F (57°C) thermal.
See DN-6935.
FSP-851RA:
Remote-test capable photoelectric detector for
use with DNR(W) duct detector housings.
See DN-6935.