ID2000 Series Operating Manual
Introduction
2
997-434-000-4, Issue 4
May 2010
The range of ID2000 Series panels, as supplied by
NOTIFIER, are designated as follows:
a. ID2000 Basic panel - 2-loop, 16-zone Analogue
Addressable Panel. Up to three 2-loop boards can
be added, to give a maximum of eight loops.
b. ID2000 Extension panel - adds a further 64 zones, to
give a maximum of 80 zones.
Each loop has the capacity for up to 99 analogue sensors
plus up to 99 modules. Details of the available sensor
and module types are given in Appendix 1.
The ID2000 Series control panel is compatible with the
laser-based Very Intelligent Early Warning (VIEW) sensor
(FSL-751E or LPX-751). Special considerations apply
when these sensors are installed or replaced (see
Section 4.8.4
).
All panels have a powerful CONTROL MATRIX feature.
This is a set of logic instructions, stored in the panel’s
internal software. It determines exactly which control
outputs (sounders, etc.) are to operate on the occurrence
of any specific Fire Alarm input, and in what manner.
Examples of the large range of options that may be
configured in a particular panel include:
a. Zoned evacuation patterns.
b. Operation of plant controls.
c. Pulsed sounder operation for alert purposes.
d. Sounders operating after a delay, or change of mode
after a delay, so as to allow time for investigation, etc.
All the control and operation functions described in this
manual can be carried out using the pushbuttons on the
front of the panel.
1.3
Cleaning
The panel case may be cleaned periodically by wiping
with a soft, damp lint-free cloth.
Do not
use any solvents.