ID2000 Series Operating Manual
Operator
Actions at Panel
16
997-434-000-4, Issue 4
May 2010
4.8.1 Zone Walk Test
If the panel is a member of an ID2000 Series panel
network, the following is displayed:
You will need to know the number of the panel at which
you wish the test to be conducted. However, the digit ‘n’
indicates the local panel (i.e. the one you are currently
standing next to); to perform a test at this panel, simply
press
.
Note:
The above question is omitted if the panel is not
part of a network.
If devices on the system are grouped into more than one
zone the following is displayed:
Type in the number of the zone you want to test, then
press
. The following is displayed:
Note:
To select more than one zone for test, repeat the
above for the
same
zone number. ‘CANCEL TEST
MODE?’ is then displayed; press
. ‘Enter ZONE
no.’ is redisplayed allowing
another
zone number
to be entered.
To start the test:
1
Press
. The panel applies a remote automatic fire
simulation control to each of the sensors in the
selected zone, and verifies that each sensor responds
correctly. This stage of the test lasts a few seconds,
during which only failures registered for this test are
reported.
2
The display subsequently shows:
where ‘n’ is the zone number. The corresponding zone
FAULT lamp illuminates steady. The panel TEST lamp
also illuminates steady. In this condition, you may:
a. Apply Fire conditions to any sensor in that Zone
(either by applying smoke or heat as appropriate,
or by operating the sensor’s internal test switch
by means of a magnet).
b. Identify the sensors in the Zone under test; their
Light-emitting-diodes (LEDs) illuminate
periodically for 1 second pulses (this is in addition
to the short-duration flashing due to normal data
scanning, if enabled).
c. Test Manual Call Points by use of the test key.
Each test operation is logged in the Event History,
recorded on the printer (if fitted) and displayed.
TEST MODE: Enter ZONE no.:
TEST ZONE (n): Confirm (
!
!
!
!
!
/X)?
ZONE n IN TEST
TEST
1 SECOND
PULSES
TEST MODE:
SLAVE no. (0=MASTER): n