ID2000 Series Operating Manual
Appendix 1
A1 - 5
997-434-000-4, Issue 4
May 2010
PANEL STATUS:
PRE-ALARM
This condition is when one or more input devices has
signalled a PRE-ALARM to the panel - i.e. a reading which
is higher than normal but not yet at the FIRE level.
This condition continues to be shown until superseded
by a higher-priority condition (i.e. FIRE) or until cleared
by pressing the RESET pushbutton.
The occurrence may have been ‘accepted’ at the panel
by pressing the ACCEPT pushbutton, if so the status is
still ‘PRE-ALARM’.
The panel indications and external equipment are as follows:
LAMP indications:
POWER (green):
ON
PRE-ALARM LAMP (amber):
if not accepted:
FLASHING
if accepted:
STEADY
All other LAMPs:
OFF
The LCD displays the message shown below:
For approximately two minutes after a Pre-Alarm is
accepted, line 2 shows a scrollable message (use
and
to scroll) giving full details about the occurrence:
‘PRE-ALARM’ (Device number) (zone) (type)
(analogue value at time of alarm) (location) (date &
time of alarm) plus indication as to whether any further
alarms exist, indicated by ‘MORE: PRESS
or
’.
Internal buzzers:
if not accepted:
Pre-alarm buzzer (high-pitched):
ON STEADY
if accepted or buzzer silenced:
Pre-alarm buzzer muted:
Intermittent - one
0.5 sec pulse ON
every 2 minutes
Circuits Controlled Internally: and
External Devices: Programmed function.
Status: PRE-ALARM
(date)
(time)
(location) (device type)