NFS2-3030 Programming Manual —
P/N 52545:K1 03/20/2012
81
Walk Test
Alter Status
4.6.4 Devices Test Selection
Figure 4.12 Devices Test Selection Screen
Soft Keys
START TROUBLE TEST:
Press this key to generate a Trouble on the selected detector.
START ALARM TEST:
Press to generate an Alarm on the selected detector.
START OBSCURATION TEST:
Press to perform an Obscuration Test on the selected Beam
detector. (Beam detectors only.)
START PREALARM TEST:
Press to perform a Prealarm Test on the selected device.
ABORT:
Press to stop the Walk Test.
T R O U B L E
P R O G M O D E A C T I V A T E D
L A K E V I E W G E N E R A L H O S P I T A L
1 0 : 2 2 : 3 4 A T U E J A N 2 5 , 2 0 1 1
W A L K T E S T I N P R O G R E S S
S E T T I N G S : B A S I C , A U D I B L E , P A N E L
S T A R T T R O U B L E T E S T S T A R T P R E A L A R M T E S T
S T A R T A L A R M T E S T
S T A R T O B S C U R A T I O N T E S T A B O R T
This field will appear only for a beam detector with an integral sensitivity test feature.
NOTE:
The Trouble, Alarm and Obscuration tests described above are additional tools provided to
ascertain the functionality of a detector. They are
not
a substitute for periodic maintenance and
sensitivity verification per NFPA 72.