78
NFS2-3030 Programming Manual —
P/N 52545:K1 03/20/2012
Alter Status
Walk Test
•
An output device activated in Advanced Walk Test will remain active and the LED will glow
steady green (if a FlashScan module) or steady red (if a CLIP module) until the
NEXT
TEST
soft key is pressed.
Conventional Devices
- Monitor modules with the Type Codes
SMOKE CONV
,
HEAT DETECT
, and
SMOKE DETECT
, and outputs with the Type Code
FORM C RESET
do not participate in Walk Test other
than blinking their addresses if they are polled in FlashScan mode unless they are used with a
FlashScan zone module. To prevent the occurrence of false alarms for conventional devices, 24 volt
power will be interrupted for up to a minute after Walk Test has been exited.
4.6.1 Walk Test Menu
Figure 4.9 Walk Test Menu Screen
Soft Keys
BASIC/ADVANCED:
Press to toggle between the two choices. Stop at the desired test.
SILENT/AUDIBLE:
This soft key is for future use. Walk test is audible.
PARAMETER:
Press to scroll through the choices. Stop at the desired parameter. Choosing the
loops parameter will bring up the Walk Test loops programming screen. (Refer to Figure 4.10.)
Choosing the Zone parameter will bring up the Zone Walk Test screen. (Refer to Figure 4.13.)
Choosing the Devices parameter will bring up the Devices Walk Test screen (Refer to Figure 4.11.
If this
parameter is
chosen…
The participating devices/points in Basic
Test will be…
The participating devices/points in
Advanced Test will be…
LOOPS
All devices/points on all the FACP SLCs
that are set to participate in Walk Test with
the exception of logic equations, whose
activation is suspended. When an input test
is initiated, only the outputs on the
corresponding loop will activate.
All devices/points on all the FACP SLCs
that are set to participate in Walk Test.
When an input test is initiated, outputs
mapped on all loops will activate.
Table 4.1 Walk Test Parameters (1 of 2)
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 0 : 2 2 : 3 4 A T U E J A N 2 5 , 2 0 1 1
W A L K T E S T
B A S I C / A D V A N C E D : B A S I C
S I L E N T / A U D I B L E : A U D I B L E
P A R A M E T E R : Z O N E A C C E P T
D I S A B L E A C S B O A R D S : Y E S B A C K