NFS2-3030 Programming Manual —
P/N 52545:K1 03/20/2012
31
Panel Program
Program
Soft Keys
ANNUNCIATOR
TYPE:
When the cursor is placed at the desired address, press this soft key to
scroll through the following list of types. Stop at the appropriate type.
POINT PROGRAMMING:
Press this soft key to proceed to the ACS Point Programming screen.
ACCEPT:
Press this soft key to save all the changes made and return to the previous screen (Panel
Program).
ACS Point Programming
ACS Point Programming can be reached by pressing
POINT PROGRAMMING
at the ACS
Programming screen. This screen allows the programmer to assign a mode and sources to each
annunciator point at the annunciator address. One ACS input may be used to control multiple SLC
output modules by listing the output points in the
SOURCE
fields. This feature applies to the
following Types:
64PT
,
64SYS
,
64SVC
,
96PT
,
96SYS
,
96SVC
, and
96DCC
.
Type
Used for
64PT
64 point annunciation
64SYS
64 point annunciation, with first 8 points reserved
64SVC
*
*
Two Level Bypass:
When an ACS board is programmed as a
64SVC
or
96SVC
type,
the operator must enter the Program/Alter Status mode of operation before pressing any
push buttons to control points on these boards. If a push button is pressed while not in
the Program/Alter Status screen, and no unacknowledged events exist, the password
screen will automatically be displayed so the operator can enter the Program/Alter
Status mode.
64-point service mode for Two Level Bypass
96PT
96 point annunciation
96SYS
96 point annunciation, with first 8 points reserved
96SVC
96-point service mode for Two Level Bypass
96DCC
96 point annunciation to be used with multiple Command Centers
UDACT
UDACT or UDACT-2, first address. Any additional UDACT or UDACT-2 annunciator addresses
should be programmed as 64PT and be sequential.
TM4
TM-4
AMG
†
†
AMG Addressing:
When using an AMG, the address it occupies (an address of 25
through 32, typically address 32) must be set to annunciator type
AMG
, and address one
must be set to annunciator type
64PT
.
AMG
FSCS
Smoke control modules set for FSCS mode
HVAC
Smoke control modules set for HVAC mode
UZC
Universal Zone Coder, first address. Any additional UZC annunciator addresses should be
programmed as 64PT and be sequential.
NOTE:
SLC output modules with releasing Type IDs may not be listed in the annunciator source
fields.
NOTE:
The NFS2-3030 supports ACM-24AT/ACM-48A annunciators and their expanders with
either 64 or 96 points at an address, as well as ACM-16AT/ACM-32A/LDM-32 annunciators with
64 points at an address.