Releasing Applications
Abort Switches
How to Program a Release Audible Circuit
The following contains information needed to program a Release Audible circuit for an SLC output
module
.
Description
An output module programmed to activate an audio or visual device when all
releasing outputs, programmed to the same Releasing Zone, turn on. Multiple outputs with the
REL
AUDIBLE
Type Code can be mapped to the same Releasing Zone. When the Releasing Zone
activates, all outputs with the
REL
AUDIBLE
Type Code activate at the same time.
Program
Select a control module to use as a releasing circuit. While programming the point
(refer to the Point Programming section of this manual for instructions),
1. Select the
REL
AUDIBLE
Type Code,
2. Enter the number of the desired Releasing Zone into the module’s zone map. The releasing
zone must be fully programmed (refer to Section 3.4.4, “Releasing Zone”, on page 57).
Example
A programming example of a control module programmed as a Release Audible circuit
for Releasing ZoneZR05.
Figure B.17 Output Module Configured as a Release Audible Circuit
NOTE:
An output with a
REL
AUDIBLE
Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit.
Type Code
REL
AUDIBLE
Type Code
RELEASE
CKT
Type Code
RELEASE
CKT
Type Code
REL
AUDIBLE
For example, an output module programmed with the
REL
AUDIBLE
Type Code activates simultaneously with other
outputs (modules A & B) programmed for ZR05.
ZR05
Monitor
Module
Detector
Detector
Detector
Output
module
SLC
output
module
A
SLC
output
module
B
Output
module