110
NFS2-3030 Programming Manual —
P/N 52545:K1 03/20/2012
Releasing Applications
Abort Switches
How to Program a Release End Bell Circuit
The following contains information needed to program a Release End Bell circuit for an SLC
output module
.
Description
An SLC output module to activate an audible or visual device when releasing
devices shut off when soak time is complete. Multiple outputs with the
REL
END
BELL
Type Code
can be mapped to the same Releasing Zone. When the soak timer has expired, all outputs with the
REL
END
BELL
Type Code activate at the same time. A
REL
END
BELL
circuit remains on until the
system is reset.
Program
Select an SLC output module to use as a Release End Bell circuit. While programming
the point (refer to the Point Programming section of this manual for instructions),
1. Select the
REL
END
BELL
Type Code,
2. Enter the number of the desired releasing zone into the module’s zone map. The releasing zone
must be fully programmed (refer to Section 3.4.2, “Module Point”, on page 51).
Example
A programming example of a control module programmed as a Release End Bell for
Releasing Zone ZR05.
Figure B.13 Output Module Configured as a Release End Bell Circuit
NOTE:
A releasing circuit with this Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit; Non-Silenceable;
No Walk Test.
Type Code
REL
END
BELL
Type Code
RELEASE
CKT
Type Code
RELEASE
CKT
Type Code
REL
AUDIBLE
For example, a module programmed with the
REL
END
BELL
Type Code activates when the ZR05 soak timer expires.
Output
module
Output
module
ZR05
Monitor
Module
Detector
Detector
Detector
SLC
output
module
SLC
output
module