Function Blocks
ON/OFF Function Block
Revision 11
HC900 Hybrid Control Designer Function Block Reference Guide
241
2/07
Table 72 ON/OFF Alarm tab configuration parameters
Properties
Function
Parameter
Index #
Parameter Description
Value or Selection
Alarm 1
Setpoint 1
20
Alarm 1 Setpoint 1 Value
- this is
the value at which you want the
alarm type chose below to activate
–99999 to 99999 in
Engineering Units
Type
N/A
Alarm 1 Setpoint 1 Type - select
what you want Alarm 1 Setpoint 1
to represent.
Selections:
NO
ALARM
PV_HIGH
PV_LOW
DEV_HIGH
DEV_LOW
SP_HIGH
SP_LOW
OUT_HIGH
OUT_LOW
Setpoint
2
21
Alarm 1 Setpoint 2 Value
Same as
Alarm 1 Setpoint 1
Type
N/A
Alarm 1 Setpoint 2 Type
Same as
Alarm 1 Setpoint 1
Alarm 2
Setpoint 1
22
Alarm 2 Setpoint 1 Value
Same as
Alarm 1 Setpoint 1
Type
N/A
Alarm 2 Setpoint 1 Type
Same as
Alarm 1 Setpoint 1
Setpoint
2
23
Alarm 2 Setpoint 2 Value
Same as
Alarm 1 Setpoint 1
Type
N/A
Alarm 2 Setpoint 2 Type
Same as
Alarm 1 Setpoint 1
Alarm Hysteresis
%
28
Alarm Hysteresis in %
0 % to 5 %