
Function Blocks
DCMP Deviation Compare Function Block
Revision 11
HC900 Hybrid Control Designer Function Block Reference Guide
127
2/07
ATTENTION
All inputs should be used or a single value should be connected to multiple inputs. Unused
inputs will default to 0.
Output
OUT = Hi (1) when any input exceeds the specified deviation from the reference value.
Block properties
Double click on the function block to access the function block properties dialog box.
Configuration parameters
Table 40 DCMP configuration parameters
Properties
Group
Parameter
Index #
Parameter Description
Value or Selection
Set
Properties
Plus
Deviation
0
Plus value deviation from
reference point
Within the range of the inputs
Minus
Deviation
1
Minus value deviation
from reference point
Within the range of the inputs