Function Blocks
HSEL High Selector Function Block
Revision 11
HC900 Hybrid Control Designer Function Block Reference Guide
177
2/07
HSEL High Selector Function Block
Description
The
HSEL
label stands for
High
Selector.
This block is part of the
Signal Selectors
category.
Function
Selects higher of two analog input values (X and Y) for output.
Indicates when Y is higher than X.
•
If X > or = Y, then:
OUT = X; YHI = OFF.
•
If X < Y, then:
OUT = Y; YHI = ON.
Input
X
= Analog value
Y
= Analog value
Output
OUT
= Higher analog value
YHI
= Digital signal. (ON when Y>X.)