Function Blocks
LSEL Low Selector Function Block
186
HC900 Hybrid Control Designer Function Block Reference Guide
Revision 11
2/07
LSEL Low Selector Function Block
Description
The
LSEL
label stands for
Low
Selector.
This block is part of the
Signal Selectors
category.
Function
Selects lower of two analog input values (X & Y) for output.
Indicates when Y is lower than X.
•
If X < or = Y, then:
OUT = X; YLO = OFF.
•
If X > Y, then:
OUT = Y; YLO = ON.
Input
X
= Analog value
Y
= Analog value
Output
OUT
= Lower analog value
YLO
= Digital signal (ON when Y<X)
Block properties
Double click on the function block to access the function block properties dialog box.
Example
H
Figure 47 shows a Function Block Diagram using an LSEL function block to monitor two analog inputs to
activate an alarm signal tag.
Figure 47 LSEL function block example