Galaxy Flex Installer Manual
Program Outputs [53]
113
27 Fire Delay (Latch)
This output is activated whenever a Fire zone is activated. Activation is delayed subject to
the
03=Abort Time
parameter. The Fire Delay output is not subject to the Re-arm
parameter. It latches on and remains active until a valid code (type 2 or above) is entered.
28 No Re-Arm (Latch)
This output is activated on a full alarm event during the set state, and is subject to the Bell
Delay parameter. The No Re-arm output is similar to the strobe output, but it stays on at the
end of the bell time, until unset.
29 Timer A (Reflex)
This output is controlled by the Timer-A option (refer to
Timers [65]
) and activates in
accordance with the programmed on and off times assigned to the function.
30 Timer B (Reflex)
This output is controlled by the Timer-B option (refer to
Timers [65]
) and activates in
accordance with the programmed on and off times assigned to the function.
Note:
If the Timer A or B
outputs are programmed as Latch mode, then they can only be
reset by a user code with access to all of the groups assigned to the relevant timer.
32 Zone Omit
This output is activated by
11=OMIT ZONES
or by
54=LINKS
, as soon as a zone is
omitted from the system. If the Output Mode attribute is assigned as:
Reflex (default), the output remains active until the zone is reinstated.
Latch, the output is reset on entry of a valid code.
34 Custom
A (Latch)
This output is activated whenever a Custom-A zone is activated.
35 Custom
B (Latch)
This output is activated whenever a Custom-B zone is activated.
37 Reset RQD (Latch)
This output is activated when a system, tamper or PA alarm occurs that needs to be reset.
Refer to
Parameters [51]
for details modifying the code levels assigned to the
06=System
Reset
,
07=Tamper Reset
and
22=PA Reset
parameters.
40 Fail Set (Latch)
Fail Set is activated if the system (or assigned groups) fails to set within the time assigned in
35=Fail to Set
(refer to
Parameters [51]
).