BEAM355, BEAM355S Single-ended 
Reflected Type Projected Beam Smoke Detector

F300-29-00 

I56-2425-007R

SPEcificATionS
GEnERAl

Range: 

16 to 230 Feet (5 to 70m)

 

230 to 328 Feet (70 to 100m) using optional accessory BEAMLRK

Sensitivity: 

25% to 50% Total Obscuration in 6 levels

 

  Level 1 = 25%

 

  Level 2 = 30%

 

  Level 3 = 40%

 

  Level 4 = 50%

 

  Level 5 = 30% to 50% (Acclimate)

 

  Level 6 = 40% to 50% (Acclimate)

Spacing: 

30 to 60 Feet (9.1 to 18.3m)

Response Time: 

ALARM: - 20 seconds typical; TROUBLE: - 30 seconds typical

Trouble Conditions: 

Beam Blockage (96% or More Obscuration)

 

Improper Initial Alignment

 

Self-compensation limit reached (service needed)

 

In Alignment mode

Test/Reset Features: 

Integral Sensitivity Test Filter (BEAM355S only, requires additional external power supply)

 

Sensitivity Filter (Incremental scale on reflector)

 

Local Alarm Test Switch

 

Local Alarm Reset Switch

 

Remote Test and Reset Switch Capability

Indicators: 

ALARM - Remote Output, Local LED (red); 

 

TROUBLE - Remote Output, Local LED (yellow), Blink Pattern Indicates Trouble Diagnostics

 

NORMAL OPERATION - Local LED (flashing green with communication)

 

ALIGNMENT AIDS - Optical Gunsight (coarse adjustment), 00 to 99 Digital Display (fine adjustment)

 

SENSITIVITY - Digital Display Readout in Percent Obscuration

Style 7 Operation: 

On-board isolators provide style 7 operation. (may be disabled via shunts on circuit board) 

 

 

ENVIRONMENTAL

Temperature: 

–22°F to 131°F (–30°C to 55°C); NOTE: for applications below 32°F (0°C) see Special Applications section of this manual.

Humidity: 

10% to 93% RH Non-condensing

Mechanical

Shipping Weight: 

3.9 lbs. (1.77 kg)

Shipping Size: 

15

 

×

 10.5

 

×

 6.5

 (381mm 

×

 267mm 

×

 165mm)

Mounting: 

Wall only without optional accessories

Wiring: 

Plug-in Terminal Blocks (12 to 22AWG)

Adjustment Angle: 

±10° Horizontal and Vertical

Paintable Trim Ring: 

May be painted using enamel or acrylic type paints

ELECTRICAL

Voltage: 

15 to 32 VDC

Standby Current: 

Avg. Standby -  

 

2mA Max. (1 communication every 5 sec. LED flashing, SLC @ 24 V)

 

Max. Alarm (LED on):   

8.5mA Max.

 

Max. Trouble (LED on):  

4.5mA Max.

 

Max. Alignment: 

 

20mA Max.

External Supply (BEAM355S only): 

VOLTAGE - 15 to 32 VDC

 

CURRENT - 0.5A Max.

Remote Output (alarm) 

VOLTAGE - 15 to 32 VDC; NOTE: Output voltage same as device input voltage.

 

CURRENT - 15mA maximum; 6mA minimum; NOTE: Output current is limited by 2.2Kohm resistor

I56-2425-00

7R

trouble thresholds. When the self-compensation circuit reaches its limit, the 
detector generates a trouble signal, indicating the need for service.

Three LEDs on the detector indicate the current status: a red LED for alarm, a 
yellow LED for trouble, and a blinking green LED for standby operation. Note: 
The panel controls the status of the red and green LEDs. The local reset but-
ton is accessible by removing the outer paintable trim ring. The yellow LED 
will blink in specific patterns to provide a diagnostic aid when diagnosing the 
cause of a trouble signal. It will also blink the amount of drift compensation 
that  has  been  used  at  the  conclusion  of  the  test.  Trouble  signals  automati-
cally reset upon removing the cause of trouble. Red and yellow LEDs can be 

GEnERAl DEScRiPTion

Fire•Lite Model BEAM355/BEAM355S is a long range projected beam smoke 

detector designed to provide open area protection. It is to be used with UL-
listed compatible control panels only. The detector consists of a transmitter/
receiver unit and a reflector. Smoke entering the area between the transmit-
ter/receiver and reflector causes a reduction in signal. When the obscuration 
reaches  alarm  thresholds  (chosen  at  the  transmitter/receiver  unit),  the  de-
tector  generates  an  alarm  signal.  Complete  blockage  of  the  beam  causes  a 
trouble signal. Slow changes in obscuration due to a build up of dirt or dust 
on the lens of the detector are compensated for by a microcontroller that con-
tinuously monitors the signal strength and periodically updates the alarm and 

inSTAllATion AnD MAinTEnAncE inSTRucTionS

One FireLite Place

Northford, CT 06472

Phone: 203.484.7161 

Summary of Contents for FireLite BEAM355

Page 1: ...g Standby 2mA Max 1 communication every 5 sec LED flashing SLC 24 V Max Alarm LED on 8 5mA Max Max Trouble LED on 4 5mA Max Max Alignment 20mA Max External Supply BEAM355S only VOLTAGE 15 to 32 VDC CURRENT 0 5A Max Remote Output alarm VOLTAGE 15 to 32 VDC NOTE Output voltage same as device input voltage CURRENT 15mA maximum 6mA minimum NOTE Output current is limited by 2 2Kohm resistor I56 2425 00...

Page 2: ... the detector and reflector cannot be mounted within 10 of each other The kit includes the hardware necessary to mount either a single transmitter receiver unit or a single reflector To mount the transmitter receiver the surface mount kit BEAMSMK must also be used If the transmitter receiver and the reflector require additional alignment range two kits are required The kit is not compatible with t...

Page 3: ...S 1 2 S MAX Tx Rx REFLECTOR C0256 00 Figure 4 Sloped ceiling peaked type 1 2 S S S 1 2 S 3 FT 0 9M MAX 3 FT 0 9M MAX MOUNT SPOT DETECTOR ANYWHERE IN THIS AREA Tx Rx REFLECTOR C0257 02 Mounting Locations Beam detectors require a stable mounting surface for proper operation A sur face that moves shifts vibrates or warps over time will cause false alarm or trouble conditions Initial selection of a pr...

Page 4: ...hrough panes of glass cannot be avoided some spe cific installation practices can help to minimize the effects of the glass These practices include avoid penetration of multiple panes of glass position the glass so that it is not perpendicular to the line of sight between the detector and the reflector A minimum of 10 off perpendicular should be considered and make certain that the glass is smooth...

Page 5: ...the product If the detector and reflector are mounted per Mounting Loca tions and Mounting Instructions sections of this manual and the alignment procedures are executed properly false alarms and nuisance trouble signals will be minimized Pre Alignment Checklist Ensure that both the detector and reflector are mounted securely to stable surfaces Ensure that all wiring is correct Ensure that termina...

Page 6: ...crease the electronic gain 4 Once satisfied that it is not possible to achieve a higher reading on the display depress the alignment switch to complete the fine adjustment step The digital display readout will turn OFF and the yellow LED will remain ON NOTE It may not be possible to achieve a value near 90 on the display during the last adjustment iteration The final value of the display will not ...

Page 7: ... illumination of the dual digital display To set the sensitivity depress the sensitivity button one time See Figure 10 Once the switch is pressed the digital display will illuminate and read the current sensitivity setting in percent obscuration To change the sensitivity continue to depress the sensitivity switch until the desired setting is achieved The digital display will turn off automatically...

Page 8: ... re ceiver unit or remotely using the remote test station The remote test station can be used with the BEAM355 BEAM355S beam smoke detector Follow instructions included with the test station for proper use See Figure 8 Remote Test Station for wiring diagram The BEAM355S is equipped with an integral sensitivity test feature that con sists of a calibrated test filter attached to a servo motor inside...

Page 9: ...tive objects in the pathway Trouble Beam Blockage Response Off 4 Quick Blinks Blink Blink Off Beam Blockage Remove blockage Faulty unit Initialization Power on Off Blink until complete Blink Blink Off Apply Power from discharged state Initialization alignment exit Off Blink until complete Blink Blink Off Depressing RESET switch after alignment Local Test BEAM355S Pass Result On Blinking the amount...

Page 10: ...Appendix II Detector Drilling Template 4 345 6 190 157 mm 110 mm Scale 1 1 F300 29 00 10 I56 2425 007R ...

Page 11: ...F300 29 00 11 I56 2425 007R ...

Page 12: ...5 512 140mm 8 465 215mm Appendix III Reflector Drilling Template Scale 1 1 F300 29 00 12 I56 2425 007R ...

Page 13: ...e reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in...

Reviews: