Ethernet Touch Call Station (ETCS)
FB 798685.GB0 / 03.20
41
4.3 Configuration error
If there are configuration errors on the ETCS,
will appear on the UI. Touch this icon to show more details
about the error.
Error
Description and Resolution
Local config error.
ETCS configuration error. Upload the configuration again.
Local audio config file error.
Local audio database error. The audio configuration cannot be found in the
database. Reconfigure the audio. Import the audio database from the ETCS
and reassign the slot then upload the configuration file again.
Local audio file not found.
The local audio cannot be found on the ETCS. Upload the audio file again.
Local audio file format error.
Local audio file format cannot be recognized by the ETCS. Upload the
audio file again.
4.4 Disk Space
Speicherinhalte
Space
Remark
Audio
4 GB
approx. 21 hours
VA Audio
1 GB
approx. 5 hours
Recording
500 MB
approx. 2,5 hours
VA Recording
500 MB
approx. 2,5 hours
Logs
400 MB
Info (200 MB) & debug (200 MB)
5 Installation
The ETCS should be installed in a room with a suitable climate as a table/console installation, or alternatively in
an upright cabinet (19"). In critical areas (e.g. due to moisture, cold, mechanical load), suitable measures must
be taken to protect the remote call stations. If necessary, an alternative installation site may be required.
.
•
For further information on assembly and installation refer to Installation Instruction VARIODYN
®
D1 devices and accessories (Part No. 798683.GB0).
•
Please follow the security advice in Chapter 13 to ensure the secure operation of the ETCS.
Summary of Contents for ETCS
Page 1: ...Ethernet Touch Call Station ETCS GB Operation Instruction 798685 GB0 03 2020 ...
Page 45: ...Ethernet Touch Call Station ETCS FB 798685 GB0 03 20 45 Notes ...
Page 46: ...Ethernet Touch Call Station ETCS 46 FB 798685 GB0 03 20 Notes ...
Page 47: ...Ethernet Touch Call Station ETCS FB 798685 GB0 03 20 47 Notes ...