NFS Supra
Page 42
HLS-MN-025 v.04
Installation and Operating Manual
www.honeywelllifesafety.es
www.hoeywelllifesafety.es
5.4.6 Disablement led indication with delay
The delay may turn on (EN54-2) the disablement led depending on the configuration.
Configuration of disablement led with delays:
Select the sounders configuration menu by
pressing at the same time the following keys:
(
KEYPAD ACCESS
=ON +
DELAY ON/OFF
=ON).
The cyclic change of the function is made by pressing the
RESET
key.
Led 1 Alarm (Red)
= ON =
Disablement led
ON with delay (
by default)
EN54-2:
Delay on/off and Disablement led
Led 2 Disablement (Yellow)
= ON =
Disablement led OFF
with delays
5.4.7 Cancel delays with 2 zones in alarm
In case of zones alarms with delays, the zones in alarm can be configured to cancel delays.
Configure: 2 Zones cancel delays
Select the configuration menu of delays cancellation with 2 zones in alarm by pressing at the
same time the following keys:
(
KEYPAD ACCESS
=ON +
MUTE BUZZER
=ON)
The cyclic change of the function is made by pressing the
RESET
key.
Led 1 Alarm (Red)
= ON =
2 Zones in alarm DO NOT cancel delays
(by default)
Led 2 Disablement (Yellow)
= ON =
2 Zones in alarm cancel delays
Reset push-button:
Change Option
(Access level 3 - Configuration)
Change
option
Reset push-button:
Change Option
(Access level 3 - Configuration)
Change
option
Configuración