NFS Supra
Page 35
HLS-MN-025 v.04
Installation and Operating Manual
www.honeywelllifesafety.es
www.hoeywelllifesafety.es
5.3 Default Configuration
NFS Supra is supplied with the following configuration, suitable for most installations.
Refer to configuration options for further information:
- Digital input: Panel
Reset
.
- Sounders without delays
(Delay 1= Delay 2 = 0 sec).
- Zone type
= Normal
(all): Immediate activation of
zone alarm
.
- Zone short circuit =
Fault.
- All zones activate all sounders.
Detectors perform
delays and call points not.
-
Disablement led on with delays
.
-
2 Zones in alarm do not cancel delays
.
-
Latching faults
.
-
Monitored main power supply and batteries
.
- Earth monitoring level
normal
.
5.3.1 Default Configuration
To restore the default configuration to the control panel:
i) Fit the
configuration jumper
(Level 3)
ii) Keep the Keypad Access push-button pressed while you are entering the access code (1221)
by pressing the zone keys in this order (
Z1, Z2, Z2 and Z1
). Control panel quits the configuration
mode and the buzzer activates with a quick intermittent sound.
iii) Remove the programming jumper. The default configuration is saved.
PROG. Jumper
Level 3 Access Jumper
Configuration