Installation and Operating Manual
www.honeywelllifesafety.es
www.hoeywelllifesafety.es
5.4.4 Sounders activation by zone (Control matrix)
Sounders activation in zones can be configured independently for detectors and call points:
delays operation (Delay 1 and Delay 2) and whether the zone activates or not the sounder.
Sounders activation by zones:
Select sounders configuration menu by pressing
SILENCE/RESOUND
=ON
Change the selected sounder by pressing
RESET
:
Led 1 Alarm (Red)
= ON =
Sounder 1
Led 2 Disablement (Yellow)
= ON =
Sounder 2
For he selected sounder:
Press the
ZONE
key to select the sounder (Sounder 1 or Sounder 2) activation
mode for each
zone (do this operation for all zones and both sounders):
Zone led
Red
Yellow
Activation mode by zone
OFF
ON
Detectors (Eco1000 or 470
) with delay / MCP (Zener 5V) without delay
ON
OFF
Detectors (Eco1000 or 470
) and MCP (Zener 5V) with delay
ON
ON
Detectors (Eco1000 or 470
) and MCP (Zener 5V) without delay
OFF
OFF
Sounder is not activated.
In order to have delayed outputs, Delay 1 or Delay 2 must be configured.
At level 1 or 2, DELAY
ON/OFF
push-button can be pressed in order to cancel operating
delays
Reset
push-button:
Change
Option
(Access
level
3
-
Configuration)
Sounder 1 or
Sounder 2
To exit this option, press
SILENCE/RESOUND
push-button again
.
Zone push-button to
select sounder
activaction
Configuration