NFS Supra
Page 15
HLS-MN-025 v.04
Installation and Operating Manual
www.honeywelllifesafety.es
www.hoeywelllifesafety.es
2.1.3 Function keys and zone keys
NFS Supra
control panel has 5 function push-buttons and a pushbutton for each zone.
The access to functions and push-button is limited to 2 access levels for users and a third access level only for
programmers.
Functions available in Access level 1 (user)
In Access level 1, the user can only visualize the system status and silence the buzzer:
KEYPAD ACCESS/LAMP TEST
:
Press this key for 3 seconds
to make a
led test
. All the leds and buzzer will activate for a few
seconds
.
BUZZER MUTE:
Press this key to silence de Buzzer.
If Buzzer Mute key is pressed while Time 1 delay (acknowledgement)
is activated, Time 2 delay (Inspection) will start.
DELAY ON/OFF:
Press this key to stop delays in operation
.
Access Level 2 (User )
All functions available in Access level 1 are also available in Access level 2.
Access Level 2 (Enable keypad)
In order to have access to user functions (level 2) and enable the keypad
: Turn the key clockwise
To ON position. Keypad access led ON indicates that level 2 is available.
If the key is not available:
press the
Keypad
key while entering the access code 1221
at the same time
,
by pressing the zone keys
Z1, Z2, Z2 and Z1
in this order. Keypad push button led will be illuminated to
indicate the access level 2. If no other push button is pressed in 3 minutes, the control panel will return to
access level 1.
Zone Keys
Function Keys
Access-Key
(User)
Operation