Honeywell
• 21
Programming
5.3.2
BACnet MS/TP monitoring values
P5.7.3.2.1
F
IELDBUS
PROTOCOL
STATUS
Fieldbus Protocol Status
tells the status of the protocol.
Table 8.
FB protocol statuses
P5.7.3.2.2
C
OMMUNICATION
STATUS
The
Communication status
shows how many error and how many good messages the frequency
converter has received. The Communication status includes a common error counter that
counts CRC and parity errors and a counter for good messages.
Only messages to the current slave in use are counted in the good messages, not MS/TP token
packages.
Table 9.
P5.7.3.2.3
A
CTUAL
INSTANCE
NUMBER
Shows the actual instance number.
P5.7.3.2.4
F
AULT
CODE
Shows BACnet MS/TP fault codes.
Table 10.
P5.7.3.2.5
C
ONTROL
WORD
Shows the
Control Word
received from the bus.
INITIALIZING
Protocol is starting up
STOPPED
Protocol is timeouted or not used
OPERATIONAL
Protocol is running
FAULTED
Major fault in protocol, requires restarting.
If fault remains contact [email protected]
Bad Frames
Good messages
0…99
Number of messages received
with errors
0…999
Number of messages received
without errors
Code
Code name
Description
0
None
1
Sole Master
No other devices on the bus
2
Duplicate MAC ID
Two devices have identical MAC ID
3
Baud rate fault
No baudrate detected by
Autobaud-
ing
(P5.7.3.1.2 Autobauding)
Summary of Contents for BacNet protocol
Page 1: ...Honeywell Installation and User Manual BacNet protocol for Variable Frequency Drives ...
Page 3: ...Honeywell 1 ...
Page 7: ...Honeywell 5 Safety ...
Page 9: ...Honeywell 7 BACnet general info ...
Page 11: ...Honeywell 9 BACnet technical data ...
Page 37: ...Honeywell 35 Fault tracing ...