Communications
Honeywell
• 30
Table 14.
NOTE:
Present Value Access Types:
R
= Read-only,
W
= Writeable,
C
= Commandable.
Commandable values support priority arrays & relinquish defaults.
High and Low limits for the objects are defined in the application. See corresponding applica-
tion for exact limits.
AV27
Maximum Frequency
Maximum Frequency
Hz
W
AV28
Accel Time
Acceleration Time
s
W
AV29
Decel Time
Deceleration Time
s
W
AV30
fb_ProcessdataIn_01
Application specific
16 bits Resolution 1
C
AV31
fb_ProcessdataIn_02
Application specific
16 bits Resolution 1
C
AV32
fb_ProcessdataIn_03
Application specific
16 bits Resolution 1
C
AV33
fb_ProcessdataIn_04
Application specific
16 bits Resolution 1
C
AV34
AnyParam ID
ID number that is used
in AV35
0 to 65535
resolution 1
W
AV35
AnyParam Value
Value of ID defined by
AV34
32 bits Value
W
AV36
*
Fb_Control_Word Lo16
Fixed Control Word First
16 bits 0-15
16 bits Resolution 1
C
AV37*
Fb_Control_Word Hi16
Fixed Control Word Last
16 bits 16-31
16 bits Resolution 1
C
AV38
Fb_Status_Word Lo16
Fixed Status Word First
16 bits 0-15
16 bits Resolution 1
R
AV39
Fb_Status_Word Hi16
Fixed Status Word Last
16 bits 16-31
16 bits Resolution 1
R
*ANSI/IEEE-754 floating point. Binary coding can be done only if the value has no decimals.
Summary of Contents for BacNet protocol
Page 1: ...Honeywell Installation and User Manual BacNet protocol for Variable Frequency Drives ...
Page 3: ...Honeywell 1 ...
Page 7: ...Honeywell 5 Safety ...
Page 9: ...Honeywell 7 BACnet general info ...
Page 11: ...Honeywell 9 BACnet technical data ...
Page 37: ...Honeywell 35 Fault tracing ...