BACnet technical data
Honeywell
• 8
3.
BACnet technical data
3.1
BACnet MS/TP protocol
Table 3.
3.2
BACnet IP protocol
Table 4.
Connections and
communications
Interface
RS-485
Data transfer method
RS-485 MS/TP, half-duplex
Transfer cable
STP (Shielded Twisted Pair), type
Belden 9841 or similar
Connector
2.5 mm
2
Electrical isolation
Functional
BACnet MS/TP
As described in ANSI/ASHRAE Stan-
dards 135-2004
Baud rate
9600, 19200, 38400 and 76800
baud(supports autobaud detection)
Connections and
communications
Interface
100BaseTX, IEEE 802.3 compatible
Data transfer method
Ethernet half/full -duplex
Data transfer speed
10/100 MBit/s, autosensing
Protocol
BACnet over UDP/IP
Connector
Shielded RJ45 connector;
NOTE:
Max
length of the non-bending part 40 mm.
Cable type
CAT5e STP
BACnet IP
As described in ANSI/ASHRAE Stan-
dards 135-2004
Default IP
Selectable: Fixed or DHCP (AutoIP)