![Honeywell Ademco Vista-12D Installation And Setup Manual Download Page 99](http://html.mh-extra.com/html/honeywell/ademco-vista-12d/ademco-vista-12d_installation-and-setup-manual_153258099.webp)
Testing the System
7-3
Dialer Communication Test
1. Enter Installer Code + 5 [TEST], then press “1” at the prompt to start the Dialer Test.
1=DIAL, 0=WALK
(no special display on Fixed-Word keypads)
The following will be displayed (accompanied by 2 beeps) if test is successful:
PHONE OKAY
(“Cd” displayed on Fixed-Word Display Keypads)
A Contact ID report will also be sent (code 601)
If the dialer test is unsuccessful, the following is displayed:
COMM FAILURE
(“FC” displayed on Fixed-Word Display Keypads)
2. Enter installer code + OFF to clear the display and exit.
Automatic Standby Battery Tests
1. An automatic test is conducted every 3 minutes to ensure that a standby battery is
present and properly connected. If a battery is not present or is not properly connected, a
“LOW BATTERY” message is displayed and, if so programmed, will be reported to the
central station.
2. A battery capacity test is automatically conducted for 2 minutes every 4 hours, beginning
4 hours after exiting the Programming mode or after powering up the system. In
addition, entry into the Test mode will also cause a battery capacity test to be initiated. If
the battery cannot sustain a load, a “Low Battery” message is displayed and, if so
programmed, will be reported to the central station.
Summary of Contents for Ademco Vista-12D
Page 2: ...Installation and Setup Guide ii ...
Page 8: ...Installation and Setup Guide 1 4 ...
Page 36: ...Installation and Setup Guide 3 10 ...
Page 100: ...Installation and Setup Guide 7 4 ...
Page 106: ...Installation and Setup Guide 8 6 ...