Installation and Setup Guide
3-6
Zone Type
Description
Type 08
24-hour Auxiliary
Alarm
•
Assign to a zone containing an emergency button, or to a zone containing
monitoring devices such as water or temperature sensors.
•
Sends a report to the central station and provides an alarm sound at the
keypad. (No siren output is provided.)
Type 09
Supervised Fire
•
Provides a fire alarm on short circuit and a trouble condition on open
circuit. A fire alarm produces a pulsing siren output.
•
This zone type is always active and cannot be bypassed.
Type 10
Interior w/Delay
•
Provides entry delay (using the programmed entry time), if tripped when
the panel is armed in the Away mode.
•
Entry Delay 1 begins whenever sensors in this zone are violated,
regardless of whether or not an entry/exit delay zone was tripped first.
•
Bypassed when the panel is armed in the Stay or Instant modes; if
armed in Night-Stay mode, zones assigned to zone list 05 (night-stay
zone list) are not bypassed when system armed in Night-Stay mode.
Type 12
Monitor Zone
•
Works as a dynamic monitor of a zone fault/trouble (not alarm). In the
case of a short/open, the message, "*ALARM*-24 Hr. Non-Burg. -#XXX "
(where XXX is the zone number) will be sent to the Central Station. The
system keypad will display a “CHECK” message indicating the
appropriate zone (but keypad beeping does not occur). Upon restoral of
the zone, the message, "*RESTORE*-24 Hr. Non-Burg. -#XXX
" will be
sent to the Central Station.
•
The “CHECK” message will automatically disappear from the keypad
dynamically, when the zone restores; a user code + off sequence is not
needed to reset the zone.
•
Faults of this zone type are independent of the system, and can exist at
the time of arming without interference.
•
Since this is a “trouble” zone type, do not use this zone type with relays
set to activate upon “alarm.”
Type 14
24 Hour Gas Monitor
•
Assigned to any zone with a gas detector.
•
The siren output will pulse when this zone type is alarmed.
•
Always active and cannot be bypassed.
Type 16
Fire w/Verification
•
Provides a fire alarm when zone is shorted, but only after alarm is
verified.
•
System verifies alarm by resetting zones for 12 seconds after short is
detected. A subsequent short circuit within 90 seconds triggers fire
alarm.
•
Provides a trouble response when zone is open.
Type 20: Arm-Stay
(BR RF devices only)
•
Arms the system in Stay mode when the zone is activated.
•
Pushbutton units send user number to the central station when
arming/disarming.
•
User number for button must be assigned.
Type 21: Arm-Away
(BR RF devices only)
•
Arms the system in Away mode when the zone is activated.
•
Pushbutton units send user number to the central station when
arming/disarming.
•
User number for button must be assigned.