MAN0443.P65 Issue 13 Aug 04
5701 Control System
05701-M-5001 A02279
CHAPTER 4 - INSTALLATION INSTRUCTIONS
4 - 17
PSU Assembly
A
B
Clearance
Width
Height
8 Way
279.4
261.9
222
41
16 Way
482.6
465.1
443
41
(2)
Insert the rack into the aperture and secure using M6, or similar
bolts, through the four mounting holes located upon the front flange
plates.
(3)
Ensure adequate support at the rear of rear access racks.
(4)
Prepare and connect the cable ends to Field Interface and Relay
Cards terminals. For terminal identification see Chapter 2. Where
possible keep sensor cables separate from the other wiring.
(5)
Ensure that the rack is properly earthed by connecting a suitable
earth cable to the earth stud located at the rear of the rack.
CAUTION
Do not apply power to the System 57 until the commissioning
procedure has been read and understood. See Chapter 5.
AC to DC PSU Table of Sizes (mm)
A
31.8
5.9
43.6
8.4
B