8 - 4
MAN0443.P65 Issue 13 Aug 04
5701 Control System
05701-M-5001 A02279
CHAPTER 8 - SPECIFICATION
LV Directive 73/23/EEC
Constructed in accordance with good engineering practice. Guided by
the principles of EN 61010/1 1990/1992.
4.
POWER SUPPLIES
Power Consumption :
Dependent upon configuration.
(System)
See Chapter 4, Section 5.
External DC Power Supply:
18V to 32V to DC Input Card.
External AC Power Supply:
85V to 264V at 47Hz to 440Hz.
(Using optional AC to DC PSU).
5.
INDIVIDUAL MODULE PARAMETERS
5.1
Interface/Relay Cards
Dimensions:
Height 112mm.
Width
25mm.
Depth 102mm.
Weight:
Field Interface
95g.
Double SPCO
155g.
Triple SPCO
205g.
Triple DPCO
245g.
High Integrity
255g.
Power:
Field Interface
0.0W.
Double SPCO
0.8W.
Triple SPCO
1.0W.
Triple DPCO
1.6W.
High Integrity
1.7W.
Relay Operation:
Selectable.
Latching/Non-Latching.
Energised/De-Energised.
Relay Contact Rating:
5A at 110V/250V ac (non inductive).
5A at 32V dc (non- inductive).
Field Terminals:
2.5mm
2
(14 AWG).