2 - 16
MAN0443.P65 Issue 13 Aug 04
5701 Control System
05701-M-5001 A02279
CHAPTER 2 - SYSTEM DESCRIPTION
5.4
Triple SPCO Relay Card (Part Number 05701-A-0328)
5.4.1 General
Provides connections between the sensor and the control card in
the same way as the Field Interface Card. In addition, single pole
relays provide voltage free contact outputs for the A1 alarm level,
A2 alarm level, A3 alarm level, fault and inhibit conditions.
5.4.2 Rear Access Connections
2
Fault NO
4
Inhibit COM
6
Inhibit NO
8
A1(1) NO
10
A2(1) COM
12
A2(1) NO
14
A3(1) NO
16
Not Connected
18
Not Connected
20
Not Connected
22
Not Connected
24
Not Connected
26
Ground
28
Sensor 01 Connection
30
Not Connected
32
Analogue O/P (-)
34
Remote Reset In
36
0V (Out/In)
Fault NC
1
Fault COM
3
Inhibit NC
5
A1(1) NC
7
A1(1) COM
9
A2(1) NC
11
A3(1) NC
13
A3(1) COM
15
Not Connected
17
Not Connected
19
Not Connected
21
Not Connected
23
Ground
25
Sensor S Connection
27
Sensor NS Connection 29
Analogue O/P (+)
31
Remote Inhibit IN
33
+24V (Out/In)
35
NC = Normally Closed.
NO = Normally Open.
COM =
Common.
Relay contact conditions refer to the no power state of the relay.
Slot
Location
User
Terminal
Reference