Mounting and Operating Instructions Doorguard for MB panels BUS-2
9
Required software: MB24/48/100 from V18.xx, MB-Secure fromV04.xx (see 1.2.2)
2.2
Door open monitoring
Programming of the Door open monitoring via WINFEM Advanced or IQ PanelControl.
- Permanent release via operation:
1. Permanent release with manual activation:
Once deactivated, the door can be accessed any number of times without a reminder signal.
Activation is performed by way of manual operation using an ID pass card or key.
2. Permanent release with automatic activation:
9
Once deactivated, the door can be remain open for any length of time without a reminder signal.
Activation is performed automatically when the door is closed.
- Programming "Manual activation" means:
The door can be opened at any time after activation. If the permissible door release time is exceeded (door
open time minus door open signal), a reminder signal is emitted every 20 seconds. The Doorguard
must then
be manually reactivated.
- Programming "Automatic activation" means
This function is intended for temporary release. Exceeding the release time results in an optical and acoustical
message (see graphic below):
Door lock release : Period in which the door may be opened (Default setting: 1 minute) when the Doorguard
is inactive.
Door open time:
Period during which the door (release contact at input 2) is permitted to remain open
after authorized opening before an optical and acoustical message is emitted.
(Default setting: 3 minutes).
Door open signal:
This period indicates how long the reminder signal of the Doorguard is activated before
expiry of the door open period. During this period, the door can be closed without an
optical or acoustical message being emitted (Default setting: 2 minutes).
Irrespective of the automatic activation, the state can be changed at all times via an operating function.