Position "Off" 

The built-in acoustic alarm is not activated.  
 
The controller front cover features 

Light-Emitting Diodes 

(LEDs)

 for indication of operating conditions: 

Yellow LED „Incorrect phase sequence“ (only 3-ph 
models) 

The yellow LED in the front cover of three-phase control-
lers indicates wether the phase sequence of the mains 
connection is correct. If the LED is illuminated, the phase 
sequence is wrong. 

Note :

 This function does not prevent the motor from 

starting and rotating in the wrong direction because it 
does not measure the phase sequence to the motor. 
Therefore, the direction of rotation of three-phase pumps 
must always be checked if the cable between pump and 
controller has been removed. 
 

Green LED „Operation“ 

The green LED illuminates when the pump is operating. 
 

Red LED „Alarm“ and „Failure“

 

- Permanent Signal 

The red Alarm-LED illuminates in case of to high liquid 
level in tank. Together with the red LED, the built-in 
acoustic alarm is activated if the switch in the front cover 
is in position „On“. Furthermore, the external fault signal 
device, if fitted, is activated. 
If the red Alarm-LED illuminates together with the green 
LED, the pump operates, but the liquid level in the tank is 
above the alarm level. The alarm is automatically reset 
when the liquid level has been lowered below the alarm 
level. 
If the red LED illuminates together with the LED „Failure“, 
the pump was stopped by thermal cutout. In this case, 
push the „Reset“ switch. If the pump still does not work, 
please contact your HOMA service. 
 

Red LED „Failure“ 
- Flash Signal 

The Failure-LED flashes when the annual maintenance is 
recommended after 2 months. 

 
Deactivating of „Maintenance flash“:  

Set the operation switch in position „Aus/Off“, then press 
the „Reset“-button. After releasing „Reset“ the LED 
„Alarm“ lights up for approx. 1 second. Within this time set 
the operation switch in position „Auto“. The flash light ex-
tinguish. 
 

Reactivating of „Maintenance flash“ (only possible by 
using ServCom Service-Controller):  

Reset the maintenance counter in the ServCom menu. 
Subsequently set the operation switch in position 
„Aus/Off“, then press the „Reset“-button. 

 
Note:  

Deactivating „Maintenance flash“ is possible starting from 
version 1.0d of the pump control (see menu in ServCom). 
„Maintenance flash“ is deactivated, if „!“ appears behind in 
ServCom the version No;  
„Maintenance flash“ is activated, if „!“ behind the version 
No. is missing. 
 

Red LED „Alarm“ 
- Flash Signal 

The Alarm-LED flashes when the control unit has moni-
tored several pump operation circuits longer than 2 min-
utes each. Please contact your HOMA service. 

Red LED Signal "Alarm" 
- Permanent signal 

The red LED illuminates in case of to high liquid level in 
tank. Together with the red LED, the built-in acoustic 
alarm is activated if the switch in the front cover is in posi-
tion „On“. Furthermore, the external fault signal device, if 
fitted, is activated. 
If the red LED illuminates together with the two green 
LEDs the pumps are operating, but the liquid level in the 
tank is above the alarm level. The alarm is automatically 
reset when the liquid level has been lowered below the 
alarm level. 
If the red LED illuminates without an illumination of the 
yellow LED „Failure“ and none or only one green LED il-
luminates, please contact your HOMA service. 
 

HOMA ServCom Controller for adjusting and monitor-
ing operation data is available as an accessory. 

 
 

6.3. Check of Direction of Rotation 

1 Ph-pumps do not require any check, as they always run 
with the correct direction of rotation. 
 
If the direction of rotation is wrong, interchange two of the 
phases of the electric power supply. Using an original 
HOMA control box with CEE-plug, this may be done by a 
180° turning of the small round pole-socket at the plug-
end with a screwdriver. 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
7. Installation

 

7.1. Installation Place

 

Please pay attention to the local regulations for con-

structions and authorisations. 

Please pay attention to the regulations for lifting 

gears and manhole. 

All underground, concret and mason's work should be 

done by an expert. 
 

7.2. Connection of pressure sensor 

By connecting the pvc hose at the control panel pay atten-
tion to perfect connection. For a perfect function tightness 
is very important and shift the hose steadily increase from 
pit to control box. Do not squeeze the hose. 
 

7.3 Installtion of pump and installation kit 

Saniquick UFT is a complete unit. With the Überwurfmut-
ter of the collectin tank, the installation kit and pump can 
install easily separate or complete. 

Summary of Contents for Saniquick UFT Series

Page 1: ...Original Betriebsanleitung Original Instruction Manual HOMA Pumpenfabrik GmbH 02 2011 Industriestr 1 D 53819 Neunkirchen Seelscheid Baureihe Series Saniquick UFT...

Page 2: ...chten Ausf hrung den einschl gigen grundlegenden Sicherheits und Gesundheitsanforderun gen der EG Maschinenrichtlinien entsprechen Bei einer nicht mit uns abgestimmten nderung der Produkte ver liert d...

Page 3: ...ienungsanleitung nicht eingehalten werden nicht haften F r Zubeh rteile gelten die gleichen Bestimmungen 3 Einsatz und Technische Beschreibung 3 1 Einsatz der Anlage Die Schmutzwasser Hebeanlage dient...

Page 4: ...etriebes 5 Transport und Lagerung Die Hebeanlage nur in senkrechter Position transpor tieren beim Transport nicht werfen oder st rzen Bei l n gerer Lagerung ist die Anlage gegen Feuchtigkeit W rme ode...

Page 5: ...h nicht einwandfrei arbeitet informieren Sie bitte unseren Kundendienst Rote LED St rung Pumpe 1 Blinksignal Blinkt zur Information 2 Monate bevor der emfohlene j hr liche Wartungstermin erreicht ist...

Page 6: ...nicht abgequetscht wird 7 3 Ein bzw Ausbau von Pumpe und Einbaugarnitur Die Hebeanlage wird als komplette Einheit geliefert Mit Hilfe der berwurfmutter am Sammelschacht kann die Einbaugarnitur und Pum...

Page 7: ...lt werden lsorte biologisch abbaubares HOMA ATOX auf Wunsch lieferbar Verbrauchtes l ist ordnungsge m zu entsorgen Um einen zuverl ssigen und st rungsfreien Betrieb der Anlage sicherzustellen empfehle...

Page 8: ...ingen 03 31 740 40 70 0 74 31 95 83 24 Naumann Pumpen GmbH Co KG G Meier GmbH Am Wall 11 Gustav Schwab Str 16 14979 Gro beeren 72762 Reutlingen 03 37 01 52 50 0 71 21 26 90 0 HEKO Pumpen GmbH Pumpen Z...

Page 9: ...in respect to their design and construction the following products in the form in which they are marketed by us conform to the relevant fundamental safety and health re quirements of the EC Machine Di...

Page 10: ...in the operating instructions The same product liability are valid for accessories 3 Application and technical description 3 1 Application The pump station Saniquick UFT is used for removal of clear w...

Page 11: ...earthing isolating transformer fault current breaker or fault voltags circuit must correspond to the guidelines set forth by the responsible power plant The voltage required in the technical data shee...

Page 12: ...eactivating Maintenance flash is possible starting from version 1 0d of the pump control see menu in ServCom Maintenance flash is deactivated if appears behind in ServCom the version No Maintenance fl...

Page 13: ...eter Pump parts and impeller Check for possible wear Replace defective parts Ball bearings Check the shaft for noisy or heavy opera tion turn the shaft by hand Replace defective ball bear ings A gener...

Page 14: ...rsatzteile An HOMA Pumpenfabrik GmbH D 53819 Neunkirchen Seelscheid Fax 0 22 47 7 02 44 Pumpentyp siehe Typenschild Baujahr siehe Typenschild Detailierte Ersatzteile 1 Pos Nr Bezeichnung Menge 2 Pos N...

Page 15: ...ription Required Quantity 2 Pos no Part description Required Quantity 3 Pos no Part description Required Quantity 4 Pos no Part description Required Quantity 5 Pos no Part description Required Quantit...

Page 16: ...be 6 06 Befestigungslasche 3 03 U Scheibe 7 01 Elektronik Steuerung 4 01 Doppelnippel 8 01 Pumpe 4 02 O Ring 4 03 Einschraubteil 13 Spare part list ATTENTION The following list contains parts that do...

Page 17: ...xisch nein ja welche Stoffe _____________________ tzend nein ja welche Stoffe _____________________ mikrobiologisch nein ja welche Stoffe _____________________ explosiv nein ja welche Stoffe _________...

Page 18: ...______________ corrosive no yes which substance __________________ microbiological no yes which substance __________________ explosive no yes which substance __________________ radioactive no yes whic...

Page 19: ...17...

Page 20: ...18...

Reviews: