OM-2098C / Operation and Maintenance Manual
60CU24 / Series 500060C / 400 Hz. Generator Set
April 01, 2005
Chapter 3-2
Page 7
6) Run-in and Periodic Check
a)
Mount the engine-generator assembly in a suitable test area and operate it for a 2-hour run-in.
b)
Shut down the engine after 2 hours and re-torque all coupling bolts to 85 foot-pounds
(115 N-m)
to
compensate for normal torque relaxation.
c)
Return the unit to normal service.
d)
After 200 hours of operation, check all coupling bolts with a torque wrench set at 85 foot-pounds
(115
N-m).
e)
Return the unit to normal service.
f)
After each additional 2,000 hours of operation
(or every year)
recheck all coupling bolts to maintain
the same torque value.