OM-2098C / Operation and Maintenance Manual
60CU24 / Series 500060C / 400 Hz. Generator Set
April 01, 2005
Chapter 2-4
Page 14
Trouble, Symptom, Condition
Probable Cause
Test, Check, and/or Remedy
Engine Controls (continued)
a.
Improper engine adjustments
and gear train timing
“Tune-up” engine in accordance
with engine manufacturer’s
operation manual.
b.
Insufficient fuel
Check low fuel level in accordance
with engine manufacturer’s
operation manual. Repair or
replace parts as required.
c.
Insufficient inlet air due to
damaged or dirty air cleaner.
Check air cleaner for “plugging”
and/or damage.
11.
Engine lacks power
d.
Restricted exhaust system
Check exhaust pipes for
restrictions. Check muffler for
clogged condition. Replace as
required.
Trouble, Symptom, Condition
Probable Cause
Test, Check, and/or Remedy
Generator Excitation Circuits
a.
Defective generator or
excitation circuit.
On REG place Regulated/
Diagnostic switch in Diagnostic
position. This applies 12 VDC
from battery to exciter field, which
should produce an indicated
output voltage of 100 +/- 20 VAC
line to neutral. If voltage produced
is within this range, the generator
is good, and trouble is in voltage
regulator circuit. Proceed to Step
b
.
b.
Defective voltage regulator
(REG)
Connect a properly working REG
board to regulator wiring
assembly, avoid short circuiting
bottom of properly working REG
board. Then start generator set
and perform tests and adjustments
according to instructions in Section
2-3. If generator set works
properly with a properly working
REG board temporarily connected,
shut off generator set and replace
defective REG board with one that
is properly working (preferably,
same REG board used for this
troubleshooting check).
1.
No (or low) generator output
voltage in all phases. Generator
operating at 400 Hz.
c.
Open fuse on REG.
Check fuses thoroughly. Replace
fuses if defective.
Summary of Contents for 60CU24
Page 2: ......
Page 4: ......
Page 203: ...ITW GSE GROUP...
Page 204: ......
Page 205: ...ITW GSE GROUP...
Page 206: ......
Page 207: ...ITW GSE GROUP...
Page 208: ......
Page 209: ...ITW GSE GROUP...
Page 210: ......
Page 211: ...ITW GSE GROUP...
Page 212: ......
Page 213: ...ITW GSE GROUP...
Page 214: ......
Page 215: ......
Page 216: ......
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ...ITW GSE GROUP...
Page 224: ......
Page 225: ......
Page 226: ......
Page 227: ......
Page 228: ......