84 (124)
8.2
Addressing and Register Mapping
8.2.1
Data From Modbus TCP Network to Serial-Subnet
Process data offset
Coil address
Holding register
0x0000 — 0x001
0x0000 — 0x000F
0x0000
0x0002 — 0x0003
0x0010 — 0x001F
0x0001
...
...
...
0x05D8 — 0x05D9
0x2EC0 — 0x2ECF
0x02EC
0x05DA — 0x05DB
0x2ED0 — 0x2EDF
0x02ED
8.2.2
Data From Serial-Subnet to Modbus TCP Network
Process data offset
Discrete input address
Input register
Holding register
0x0000 — 0x001
0x0000 — 0x000F
0x0000
0x0800
0x0002 — 0x0003
0x0010 — 0x001F
0x0001
0x0801
...
...
...
...
0x05D8 — 0x05D9
0x2EC0 — 0x2ECF
0x02EC
0x0AEC
0x05DA — 0x05DB
0x2ED0 — 0x2EDF
0x02ED
0x0AED
8.2.3
Idle Mode
Transaction
Holding Register
Description
Enter/Exit Idle Mode
0x1004
Used by the Modbus TCP client to
indicate an idle/offline mode on the
network.