70 (124)
7.9.6
Timeout Time Settings
Connection timeout
Specify how long a Modbus TCP connection may be idle before it is closed by the Communicator.
The default value is 60 seconds
Process data active timeout
Specify the maximum allowed time between two incoming messages in steps of 10 ms.
If this time is exceeded, the high level network is considered to be offline.
The data sent to the sub-network is frozen.
A value of 0 disables this feature, i.e. the high level network can never go offline.
The default value is 0 ms.