More user manuals on
ManualsBase.com
“D” Function
Func.
Code
Name /
SRW Display
Description
Run
Mode
Edit
Units
Scaled output frequency
monitor
D007
F-Cnv
00000.00
Displays the output frequency
scaled by the constant in B086.
Decimal point indicates range:
XX.XX
0.00 to 99.99
XXX.X
100.0 to 999.9
XXXX.
1000. to 9999.
XXXX
1000 to 9999
(x10=10000 to 99999)
−
Hz times
constant
Output voltage monitor
D013
Vout
00000V
Voltage of output to motor,
Range is 0.0 to 600.0V
−
V
Cumulative operation
RUN time monitor
D016
RUN
0000000hr
Displays total time the inverter has
been in RUN mode in hours.
Range is 0 to 9999 / 1000 to 9999 /
⎡
100 to
⎡
999 (10,000 to 99,900)
−
hours
Cumulative power-on time
monitor
D017
RUN
0000000hr
Displays total time the inverter has
been powered up in hours.
Range is 0 to 9999 / 1000 to 9999 /
⎡
100 to
⎡
999 (10,000 to 99,900)
−
hours
Cooling Fin temperature
monitor
D018
TH-Fin
0000.0 C
Temperature of the cooling fin.
(0.0~200)
−
°
C
Trip Event and History Monitoring
The trip event and history monitoring features lets you cycle through related
information using the keypad. See “
Monitoring Trip Events, History, & Conditions
” on
page 6-5 for more details.
“D” Function
Func.
Code
Name /
SRW Display
Description
Run
Mode
Edit
Units
Trip counter
D080
ERR CNT
00000
Number of trip events,
Range is 0. to 9999
−
events
Trip monitor 1
D081
ERR1
########
−
Trip monitor 2
D082
ERR2
########
−
−
Trip monitor 3
D083
ERR3
########
Displays trip event information:
•
Error code
•
Output freq. at trip point
•
Motor current at trip point
•
DC bus voltage at trip point
•
Cumulative inverter operation
time at trip point
•
Cumulative power-ON time at
trip point
−
−
DC bus voltage monitor
D102
Vpn
0000.0Vdc
Voltage of DC bus inside inverter,,
Range is 0.0 to 999.9
−
V
Electronic thermal monitor
D104
E-THM
0000.0%
Accumulated value of electronic
thermal detection, range is from 0.0
to 100.0
−
%
3
−
7
Confi
guri
ng Driv
e
Parameters