Analog Input Current/Voltage Select
The [AT] terminal selects whether the inverter uses the voltage [O] or current [OI]
input terminals for external frequency control. When intelligent input [AT] is ON, you
can set the output frequency by applying a current input signal at [OI]-[L]. When the
[AT] input is OFF, you can apply a voltage input signal at [O]-[L] to set the output
frequency. Note that you must also set parameter A001 = 01 to enable the analog
terminal set for controlling the inverter frequency.
Option
Code
Terminal
Symbol
Function Name
State
Description
ON
16
AT
Analog Input
Voltage/Current
Select
OFF
See the table down below
Valid for inputs:
C001~C005
Required settings
A001 = 01
Notes:
•
If the [AT] option is not assigned to any
intelligent input terminal, then inverter
recognizes [AT] = OFF in following table.
•
Be sure to set the frequency source setting
A001=01 to select the analog input terminals.
Example (default input configuration shown
for –FU models; –FE models require input
configuration—see
page 3–49
):
See I/O specs on
page 4–6.
Combination of A005 setting and [AT] input for analog input activation.
A005
[AT] Input
Analog Input Configuration
ON
Keypad Pot
02
OFF
[O]
ON
Keypad Pot
03
OFF
[OI]
04
(ignored)
[O]
05
(ignored)
[OI]
Note that you cannot give [O] and [OI] input at the same time on X200 inverter.
5
4
3
2
1
L
PCS P24
AT
AM H
O OI
L
Å
+ -
4-20 mA
0-10 V
4
−
22
Operatio
ns and
Monitori
ng