The following table shows the available analog input settings. Parameter A005 and the
input terminal [AT] determine the External Frequency Command input terminals that
are available, and how they function. The analog inputs [O] and [OI] use terminal [L] as
the reference (signal return).
A005
[AT] Input
Analog Input Configuration
ON
Keypad Pot
02
OFF
[O]
ON
Keypad Pot
03
OFF
[OI]
04
(ignored)
[O]
05
(ignored)
[OI]
NOTE: You cannot give [O] and [OI] input simultaneously on X200 series inverter.
Other Analog Input-related topics:
•
“Analog Input Settings” on page 3–13
•
“Additional Analog Input Settings” on page 3–28
•
“Analog Signal Calibration Settings” on page 3–61
•
“Analog Input Current/Voltage Select” on page 4–22
•
“ADD Frequency Enable” on page 4–30
•
“Analog Input Disconnect Detect” on page 4–44