It is possible for the inverter to retain the frequency set from the [UP] and [DWN]
terminals through a power loss. Parameter C101 enables/disables the memory. If
disabled, the inverter retains the last frequency before an UP/DWN adjustment. Use
the [UDC] terminal to clear the memory and return to the original set output frequency.
Option
Code
Terminal
Symbol
Function Name
State
Description
ON
Accelerates (increases output frequency) motor
from current frequency
27
UP
Remote Control UP
Function (motorized
speed pot.)
OFF Output to motor operates normally
ON
Decelerates (increases output frequency) motor
from current frequency
28
DWN
Remote Control
DOWN Function
(motorized speed pot.)
OFF Output to motor operates normally
ON
Clears the Up/Down frequency memory
29
UDC
Remote Control Data
Clear
OFF No effect on Up/Down memory
Valid for inputs:
C001~C005
Required settings
A001 = 02
Notes:
•
This feature is available only when the frequency
command source is programmed for operator
control. Confirm A001 is set to 02.
•
This function is not available when [JG] is in use.
•
The range of output frequency is 0 Hz to the value
in A004 (maximum frequency setting).
Example (default input configuration shown—see
page 3–49
):
See I/O specs on
page 4–6.
•
The minimum ON time of [UP] and [DWN] is 50 ms.
•
This setting modifies the inverter speed from using F001 output frequency setting as a starting point.
5
4
3
2
1
L
PCS P24
UP
DWN
4
−