The following table lists the holding registers for the “B” Group Fine Tuning Functions.
List of Holding Registers
Network Data
Func.
Code
Name
R/W
Description
Reg.
Range
Res.
B001 Selection of automatic
restart mode
R/W Select inverter restart method,
Four option codes:
00
…
Alarm output after trip, no
automatic restart
01
…
Restart at 0Hz
02
…
Resume operation after
frequency matching
03
…
Resume previous freq. after
freq. matching, then
decelerate to stop and
display trip info
10A5h
0, 1, 2, 3
−
B002 Allowable under-
voltage power failure
time
R/W The amount of time a power
input under-voltage can occur
without tripping the power
failure alarm. Range is 0.3 to 25
sec. If under-voltage exists
longer than this time, the
inverter trips, even if the restart
mode is selected.
10A6h
3 to 250
0.1 sec
B003 Retry wait time before
motor restart
R/W Time delay after under-voltage
condition goes away, before the
inverter runs motor again.
Range is 0.3 to 100 seconds.
10A7h
3 to 1000
0.1 sec
B004 Instantaneous power
failure / under-voltage
trip alarm enable
R/W Two option codes:
00
…
Disable
01
…
Enable
10A8h
0, 1
−
B005 Number of restarts on
power failure / under-
voltage trip events
R/W Two option codes:
00
…
Restart 16 times
01
…
Always restart
10A9h
0, 1
−
B011 Start freq to be used in
case of freq pull-in
restart
R/W Three option codes:
00
…
freq at previous shutoff
01
…
start from max. Hz
02
…
start from set frequency
1170
0, 1, 2
−
B012 Level of electronic
thermal setting
R/W
10ADh
B212 Level of electronic
thermal setting, 2nd
motor
R/W
Set a level between 20% and
100% for the rated inverter
current.
1527h
2000 to
10000
0.01 %
B013 Electronic thermal
characteristic
R/W
10AEh
B213 Electronic thermal
characteristic, 2nd
motor
R/W
Select from three curves, option
codes: *1
00
…
Reduced torque 1
01
…
Constant torque
02
…
Reduced torque 2
1528h
0, 1, 2
−
B
−
31
Appe
ndix B