More user manuals on
ManualsBase.com
List of Holding Registers
Network Data
Func.
Code
Name
R/W
Description
Reg.
Range
Res.
B133 DC bus AVR
selection
R/W Two option codes:
00
…
Disabled
01
…
Enabled
1176h
0, 1
−
B134 Threshold voltage of
DC bus AVR setting
R/W Setting of threshold voltage of DC bus
voltage to start DC bus AVR function.
Range is:
200V class
…
330 to 395
400V class
…
660 to 790
1177h 330 to 395,
660 to 790
1 V
B140 Over-current trip
suppression
R/W Two option codes:
00
…
Disable
01
…
Enable
10F7h
0, 1
−
B150 Carrier mode
R/W Automatically reduces the carrier
frequency as the ambient temperature
increases.
00
…
Disable
01
…
Enable
10F8h
0, 1
−
B151 Selection of RDY
function
R/W Select Ready function.
00
…
Disable
01
…
Enable
10F9h
0, 1
−
Note 1:
Assume that the inverter current rating is 10000 (for B013/B213).
B
−
35
Appe
ndix B