Inverter Parameter Setup
–
The inverter has several settings related to Modbus communications. The table
below lists them together. The Required column indicates which parameters must
be set properly to allow communications. You may need to refer to the host
computer documentation in order to match some of its settings.
Func.
Code
Name
Required
Settings
A001
Frequency source
03
00…Keypad potentiometer
01…Control terminal
02…Function F001 setting
03…Modbus network input
10…Calculate function output
A002
Run command source
03
01…Control terminal
02…Run key on keypad, or digital
operator
03…Modbus network input
C071
Communication speed
05
03 2400 bps
04 4800 bps
05 9600 bps
06 19.2k bps
07 38.4k bps
08 57.6k bps
09 76.8k bps
10 115.2k bps
C072
Modbus Address
1
Network address, range is 1 to
247
C074
Communication parity
00
00…No parity
01…Even parity
02…Odd parity
C075
Communication stop bit
1
Range is 1 or 2
C076
Communication error
select
00
00…Trip (Error code E60)
01…Decelerate to a stop and trip
02…Disable
03…Free run stop (coasting)
04…Decelerate to a stop
C077
Communication error
time-out
1.00
Comm. Watchdog timer period,
range is 0.00 to 99.99 sec.
C078
Communication wait
time
10
Time the inverter waits after
receiving a message before it
transmits. Range is 0. to 1000.
ms
Summary of Contents for WJ-0001S
Page 2: ...Hitachi Solar Water Pump Inverter System KHKSCO GROUP ...
Page 16: ...Ii Single phase 200V 0 1 to 0 4kW Three phase 200V 0 1 to 0 75kW ...
Page 17: ...Ii ...
Page 18: ...Ii ...
Page 19: ...Solar Water System 4 Wiring details ...
Page 27: ...Operating Principle 5 And Hardware ...
Page 30: ...System Start up 6 ...
Page 42: ...Network Communication 7 ...