I
i
Fuse Size
The unit shall be connected with a Listed Cartridge Nonrenewable fuse or Inverse
time circuit breaker, rated 600 Vac with the current ratings as shown in the table
below
Model No.
Fuse
Inverse Time
Circuit Breaker
Type E CMC
Type
Rating(Maximum A)
Rating (Maximum
A)
WJ
-0001
S
Class
J
10 A, AIC 200 kA
30A
MMS-32H,
240V,40A
WJ
-0002
S
Class
J
10 A, AIC 200 kA
WJ
-0004
S
Class
J
10 A, AIC 200 kA
WJ
-0007
S
Class
J
15 A, AIC 200 kA
WJ
-0015
S
Class
J
15 A, AIC 200 kA
WJ
-0022
S
Class
J
20 A, AIC 200 kA
WJ
-0004H
Class
J
10 A, AIC 200 kA
20A
MMS-32H,
480V,40A or
MMS-63H,
480V,52A
WJ
-0007H
Class
J
10 A, AIC 200 kA
WJ
-0015H
Class
J
10 A, AIC 200 kA
WJ
-0022H
Class
J
10 A, AIC 200 kA
WJ
-0030H
Class
J
15 A, AIC 200 kA
WJ
-0040H
Class
J
15 A, AIC 200 kA
WJ
-0055H
Class
J
30 A, AIC 200 kA
40A
WJ
-0075H
Class
J
30 A, AIC 200 kA
WJ
-0110H
Class
J
50 A, AIC 200 kA
WJ
-0150
H
Class
J
50 A, AIC 200 kA
Summary of Contents for WJ-0001S