Fault Codes
All fault come in parameters D081 to d086, means Hitachi drive can store last 6 fault
history.
Error
Code
Name
Cause(s)
E01
Over-current event while at
constant speed
The inverter output was short-circuited, or the
motor shaft is locked or has a heavy load. These
conditions cause excessive current for the
inverter, so the inverter output is turned OFF. The
dual-voltage motor is wired incorrectly.
E02
Over-current event during
deceleration
E03
Over-current event during
acceleration
E04
Over-current event during
other conditions
E05
Overload protection
When a motor overload is detected by the
electronic thermal function, the inverter trips and
turns OFF its output.
E06
Braking resistor overload
protection
When the BRD operation rate exceeds the
setting of "b090", this protective function shuts off
the inverter output and displays the error code.
E07
Over-voltage protection
When the DC bus voltage exceeds a threshold,
due to regenerative energy from the motor.
E08
EEPROM error
When the built-in EEPROM memory has
problems due to noise or excessive temperature,
the inverter trips and turns OFF its output to the
motor.
E09
Under-voltage error
A decrease of internal DC bus voltage below a
threshold results in a control circuit fault. This
condition can also generate excessive motor heat
or cause low torque. The inverter trips and turns
OFF its output.
E10
Current detection error
If an error occurs in the internal current detection
system, the inverter will shut off its output and
display the error code.
E11
CPU error
A malfunction in the built-in CPU has occurred,
so the inverter trips and turns OFF its output to
the motor.
E12
External trip
A signal on an intelligent input terminal
configured as EXT has occurred. The inverter
trips and turns OFF the output to the motor.
E13
USP
When the Unattended Start Protection (USP) is
enabled, an error occurred when power is applied
while a Run signal is present. The inverter trips
and does not go into Run Mode until the error is
cleared.
E14
Ground fault
The inverter is protected by the detection of
ground faults between the inverter output and the
Summary of Contents for WJ-0001S
Page 2: ...Hitachi Solar Water Pump Inverter System KHKSCO GROUP ...
Page 16: ...Ii Single phase 200V 0 1 to 0 4kW Three phase 200V 0 1 to 0 75kW ...
Page 17: ...Ii ...
Page 18: ...Ii ...
Page 19: ...Solar Water System 4 Wiring details ...
Page 27: ...Operating Principle 5 And Hardware ...
Page 30: ...System Start up 6 ...
Page 42: ...Network Communication 7 ...