– 96 –
[No operation or abnormal operation]
Is AC220-240V
being
supplied to terminal L and N?
“Be sure terminal L,N and
A,B are properly connected.
”
Is the 25A
fuse normal?
If the 25A fuse has blown, be aware
that other parts may also be
defective (mainly
, varistor 2, diode
stack, smoothing capacitors, system
power module, etc.).
No
Ye
s
CHECKING THE OUTDOOR UNIT ELECTRICAL PARTS
Replace any defective parts.
Is the power circuit normal?
See the description on
power circuit for details.
Is 5V being generated
between Pin
4
(0V) and pin
3
(5V) at CN 19 (test pin)?
Operate the outdoor unit
according to the instruction
“How to operate the outdoor
unit independently
”.
How did the self-diagnosis
lamp (LD301) light?
Is the switching power circuit OK?
Has the 5A fuse blown?
See the self-diagnosis lamp
lighting mode.
Check to see whether the
connected C and D cable
correctly? If reversed, correct the
cable connection.
Replace any defective parts.
If the 5A fuse has blown, the
switching transformer (T1),
varistor 2, R716, etc. may
also be defective.
()
No
Ye
s
Ye
s
No
Ye
s
0305E Pg 90-109
4/1/06, 11:01 AM
96
Summary of Contents for Summit RAC-70YH5
Page 36: ... 35 CIRCUIT DIAGRAM MODEL RAS 70YH5 0305E Pg 35 4 1 06 10 52 AM 1 ...
Page 37: ... 37 CIRCUIT DIAGRAM MODEL RAC 70YH5 0305E Pg 37 4 1 06 10 53 AM 1 ...
Page 39: ... 40 MODEL RAC 70YH5 MAIN P W B 0305E Pg 39 42 4 1 06 10 53 AM 40 ...
Page 40: ... 41 MAIN P W B NF P W B CAPA P W B 0305E Pg 39 42 4 1 06 10 53 AM 41 ...
Page 42: ... 43 51 53 53 55 57 49 29 66 22 0305E Pg 43 4 1 06 10 54 AM 1 ...
Page 86: ... 94 6 Check the main P W B power circuit 0305E Pg 90 109 4 1 06 11 01 AM 94 ...
Page 87: ... 95 CHECKING THE REMOTE CONTROLLER 0305E Pg 90 109 4 1 06 11 01 AM 95 ...
Page 92: ... 100 0305E Pg 90 109 4 1 06 11 01 AM 100 ...
Page 102: ...HITACHI PM NO 0305E Printed in Malaysia RAS 70YH5 RAC 70YH5 0305E cover 4 1 06 12 03 PM 2 ...