(4) Cause Code of Indoor Unit Stoppage ( )
Code
(SEG1)
Item
Code
(SEG1)
Item
Operation OFF, Power OFF
Instantaneous Overcurrent of Inverter;
Electronic Thermal Activation of Inverter Retry;
Abnormal Current Sensor of Inverter Retry.
Thermo-OFF
Retry due to Inverter Voltage Decrease;
Retry due to Inverter Overvoltage
Alarm
Electronic Valve Opening Difference
Protection
Freeze Protection; Overheating Protection
Forced Thermo-OFF for Oil Return
Instantaneous Power Failure at the Outdoor Unit
The Outdoor Unit Hot Start
Instantaneous Power Failure at the Indoor Unit
Retry due to High Pressure Decrease
Stoppage of Cooling Operation due to High/Low Outdoor
Air Temperature
Stoppage of Heating Operation due to High Outdoor Air
Temperature
Cooling Air Discharge Temperature Decrease
Demand. Forced Stoppage
Forced Thermo-OFF
Retry due to Pressure Ratio Decrease
Forced Thermo-OFF
Retry due to Ps Increase
Retry due to Abnormal Operating Mode
(4-Way Valve Switching Failure)
Retry due to Pd Increase
Retry after Defrosting Operation
Retry due to Discharge Gas Temperature Increase; Retry
due to Low Pressure Decrease
Forced Thermo-OFF for the Indoor Units Rotation
Retry due to Discharge Gas SUPERHEAT
Decrease
Forced Thermo-OFF for the Outdoor Unit Control
Notes:
●
The cause code of indoor unit stoppage is not always “ ” (Alarm) during stoppage by the abnormality.
If the unit is under Thermo-OFF by other cause of stoppage before “ ” (Alarm) occurs, the previous cause code of indoor unit
stoppage remains.
●
When the communication between the driver board and the outdoor unit PCB is disconnected for 30
seconds, the outdoor micro-computer will be reset. Accordingly when the alarm code “ ”
(Communication Failure between Driver Board and Outdoor Unit PCB) occurs, the cause code of indoor unit stoppage may be
indicated “ ”.
●
When the communication between the indoor unit and the outdoor unit is disconnected for 3 minutes, the
indoor micro-computer will be reset. Accordingly when the alarm code “ ”
(Communication Failure between Indoor Unit and Outdoor Unit) occurs, the cause code of indoor unit stoppage may be
indicated “ ”.
TROUBLESHOOTING
Summary of Contents for Set Free mini-HNRQ1 Series
Page 8: ...1 Installation ...
Page 50: ...43 Troubleshooting ...
Page 60: ...53 d Noise Filter Board NF1 TROUBLESHOOTING ...
Page 123: ...121 Maintenance ...
Page 153: ...External Input Output and Function Setting 151 ...
Page 167: ...Field Work Instructions 165 ...
Page 172: ...Service Parts List 170 ...
Page 175: ...173 SERVICE PARTS LIST RAS 3 0HNBRKQ1 RAS 3 5HNBRKQ1 ...
Page 176: ...174 SERVICE PARTS LIST RAS 3 0HNBRKQ1 RAS 3 5HNBRKQ1 ...
Page 177: ...175 SERVICE PARTS LIST RAS 4 0HNBRKQ1 RAS 4 5HNBRKQ1 RAS 5 0HNBRKQ1 ...
Page 178: ...176 SERVICE PARTS LIST RAS 4 0HNBRKQ1 RAS 4 5HNBRKQ1 RAS 5 0HNBRKQ1 ...
Page 179: ...177 SERVICE PARTS LIST RAS 6 0HNBRKQ1 RAS 6 5HNBRKQ1 ...
Page 180: ...178 SERVICE PARTS LIST RAS 6 0HNBRKQ1 RAS 6 5HNBRKQ1 ...
Page 183: ...181 SERVICE PARTS LIST RAS 7 0HNBRMQ1 RAS 8 0HNBRMQ1 ...
Page 184: ...182 SERVICE PARTS LIST RAS 7 0HNBRMQ1 RAS 8 0HNBRMQ1 ...
Page 185: ...183 SERVICE PARTS LIST RAS 10HNBRMQ1 RAS 11HNBRMQ1 RAS 12HNBRMQ1 ...
Page 186: ...184 SERVICE PARTS LIST RAS 10HNBRMQ1 RAS 11HNBRMQ1 RAS 12HNBRMQ1 ...
Page 187: ...HS2019266A ...