8
INSTALLATION
1.4 Model of Outdoor Unit
The
number of indoor units that can be connected to an outdoor unit is defined in the following table :
Table 1.1 System Combination
Outdoor Unit Type
Min. Total Capacity of
the indoor units can be
connected
(kW)
Max. Total Capacity of
the indoor units can be
connected
(kW)
Numbers of the indoor
units can be connected
(Q’ty)
Min. Capacity at
Individual Operation
(kW)
RAS-3.0HNBRKQ1
4.0
10.40
2~4
2.2
RAS-3.5HNBRKQ1
5.0
13.00
2~5
2.2
RAS-4.0HNBRKQ1
5.6
14.56
2~6
2.2
RAS-4.5HNBRKQ1
6.0
15.60
2~6
2.2
RAS-5.0HNBRKQ1
7.0
18.20
2~7
2.2
RAS-6.0HNBRKQ1
8.0
20.80
2~8
2.2
RAS-6.5HNBRKQ1
9.0
23.40
2~9
2.2
RAS-7.0HNBRMQ1
10.0
26.00
2~10
2.2
RAS-8.0HNBRMQ1
11.2
29.10
2~10
2.2
RAS-10HNBRMQ1
14.1
36.50
2~10(13)
△
2.2
RAS-11HNBRMQ1
15.5
40.30
2~10(14)
△
2.2
RAS-12HNBRMQ1
16.8
43.60
2~10(15)
△
2.2
Notes:
(1) The connectable indoor unit capacity ratio can be calculated as follows:
Connectable Indoor Unit Capacity Ratio = Total Indoor Unit Capacity / Total Outdoor Unit Capacity.
(2) It is suggested that the total capacity of indoor units which are operated simultaneously should not exceed the capacity of outdoor
units under the following conditions. Otherwise, there is a decrease in operating performance.
●
When there are some 4-way cassette indoor units and high wall indoor units in the system;
●
When the outdoor air temperature is 43°C or more during the outdoor unit cooling operation;
●
When the outdoor air temperature is lower than -10°C during the outdoor unit heating operation.
(3) When operating the outdoor unit under low heating load conditions and the outdoor temperature is 15°C WB or more, only one indoor
unit is in the operation, the outdoor unit will be Thermo-OFF* to protect the compressor from failure.
(4) *: When RAS-7.0~12HNBRMQ1 outdoor units are connected with the RCIM-0.8FSN4 or RCD-0.8~1.0FSN3 or RCS-0.8~1.0FSN,
if only one of these indoor unit is operating in cooling mode, the minimum outdoor temperature is limited to 5°C DB.
(5) For the same system, if the connectable indoor unit capacity ratio is over than 100%, and which all the indoor units operate
simultaneously, capacity of every indoor unit should be less than its rated capacity.
(6)
△ :
When the number of indoor units which are connected to the model of RAS-10~12HNBRMQ1 outdoor unit is over than 10 units,
the following restrictions are also required to meet.
(a) The piping system must be divided into two main pipes, the total capacity and the number of the units connected to each main
pipe should be as equal as possible.
(b) The maximum height difference between outdoor and indoor units is 30 meters and the maximum height difference between indoor
units is 10 meters, the longest piping length between the branch pipe to the connected indoor unit is 10 meters.
(c) The connectable indoor unit capacity ratio should not be more than 105%.
(d) Only 0.8~4.0HP of ducted indoor units can be selected.
No.1
No.10
No.2
No.3
No.4
No.5
No.6
No.7
No.8
No.9
No.11
No.12
No.13
No.14
No.15
*Thermo-ON: The outdoor unit and some indoor units are running;
Thermo-OFF: The outdoor unit and some indoor units are standby, but don’t run.
Summary of Contents for Set Free mini-HNRQ1 Series
Page 8: ...1 Installation ...
Page 50: ...43 Troubleshooting ...
Page 60: ...53 d Noise Filter Board NF1 TROUBLESHOOTING ...
Page 123: ...121 Maintenance ...
Page 153: ...External Input Output and Function Setting 151 ...
Page 167: ...Field Work Instructions 165 ...
Page 172: ...Service Parts List 170 ...
Page 175: ...173 SERVICE PARTS LIST RAS 3 0HNBRKQ1 RAS 3 5HNBRKQ1 ...
Page 176: ...174 SERVICE PARTS LIST RAS 3 0HNBRKQ1 RAS 3 5HNBRKQ1 ...
Page 177: ...175 SERVICE PARTS LIST RAS 4 0HNBRKQ1 RAS 4 5HNBRKQ1 RAS 5 0HNBRKQ1 ...
Page 178: ...176 SERVICE PARTS LIST RAS 4 0HNBRKQ1 RAS 4 5HNBRKQ1 RAS 5 0HNBRKQ1 ...
Page 179: ...177 SERVICE PARTS LIST RAS 6 0HNBRKQ1 RAS 6 5HNBRKQ1 ...
Page 180: ...178 SERVICE PARTS LIST RAS 6 0HNBRKQ1 RAS 6 5HNBRKQ1 ...
Page 183: ...181 SERVICE PARTS LIST RAS 7 0HNBRMQ1 RAS 8 0HNBRMQ1 ...
Page 184: ...182 SERVICE PARTS LIST RAS 7 0HNBRMQ1 RAS 8 0HNBRMQ1 ...
Page 185: ...183 SERVICE PARTS LIST RAS 10HNBRMQ1 RAS 11HNBRMQ1 RAS 12HNBRMQ1 ...
Page 186: ...184 SERVICE PARTS LIST RAS 10HNBRMQ1 RAS 11HNBRMQ1 RAS 12HNBRMQ1 ...
Page 187: ...HS2019266A ...