![Hitachi Set Free mini-HNRQ1 Series Service Manual Download Page 47](http://html.mh-extra.com/html/hitachi/set-free-mini-hnrq1-series/set-free-mini-hnrq1-series_service-manual_2139434047.webp)
40
OPERATION
(7) During the test run, if any malfunction happens, please examine and clear it by referring to the table of
alarm codes.
(8) If the indicated number of the wired controller is different with the actual connected indoor units, the
auto-address function is not performed correctly due to incorrect wiring. Turn off the power supply and
correct the wiring after checking the following points:
Indicated Number
Malfunction
Turn off the power supply to check
None
●
Power supply for indoor unit is not turned
on or incorrect wiring;
●
Power supply for outdoor unit is not turned
on or incorrect wiring;
●
Incorrect wiring of wired controller.
●
The terminal block for transmission wiring in the
indoor unit;
●
The terminal block for transmission wiring in the
wired controller;
●
The wiring connected to the wrong terminals;
●
The screws for the terminal block are loosen.
Less than the actual
connected
●
Power supply for indoor unit is not turned on;
●
Disconnect the transmission cables between outdoor unit and indoor units.
7. Safety and Control Device Setting
The compressor is protected by the following devices and their combinations:
(1) High Pressure Switch: This switch cuts out the operation of the compressor when the discharge pressure
exceeds the setting.
(2) Crankcase Heater: This band type heater protects against oil foaming during cold starting, as it is
energized while the compressor is stopped.
Model
RAS-3.0~
3.5HNBRKQ1
RAS-4.0~
6.5HNBRKQ1
RAS-7.0~
8.0HNBRMQ1
RAS-10~
12HNBRMQ1
High Pressure Switch
Automatic Reset, Non-Adjustable
Automatic Reset, Non-Adjustable
Cut-Out
MPa
4.15
-0.05
-0.2
4.15
-0.05
-0.2
4.15
-0.05
-0.2
4.15
-0.05
-0.2
Cut-In
MPa
3.2
+0.15
-0.2
3.2
+0.15
-0.2
3.2
+0.15
-0.2
3.2
+0.15
-0.2
Breaker
A
32
40
25
40
Crankcase Heater
W
24
28
80
80
CCP Timer
Setting Time
Min
Non-Adjustable
3
Non-Adjustable
3
Non-Adjustable
3
Non-Adjustable
3
Summary of Contents for Set Free mini-HNRQ1 Series
Page 8: ...1 Installation ...
Page 50: ...43 Troubleshooting ...
Page 60: ...53 d Noise Filter Board NF1 TROUBLESHOOTING ...
Page 123: ...121 Maintenance ...
Page 153: ...External Input Output and Function Setting 151 ...
Page 167: ...Field Work Instructions 165 ...
Page 172: ...Service Parts List 170 ...
Page 175: ...173 SERVICE PARTS LIST RAS 3 0HNBRKQ1 RAS 3 5HNBRKQ1 ...
Page 176: ...174 SERVICE PARTS LIST RAS 3 0HNBRKQ1 RAS 3 5HNBRKQ1 ...
Page 177: ...175 SERVICE PARTS LIST RAS 4 0HNBRKQ1 RAS 4 5HNBRKQ1 RAS 5 0HNBRKQ1 ...
Page 178: ...176 SERVICE PARTS LIST RAS 4 0HNBRKQ1 RAS 4 5HNBRKQ1 RAS 5 0HNBRKQ1 ...
Page 179: ...177 SERVICE PARTS LIST RAS 6 0HNBRKQ1 RAS 6 5HNBRKQ1 ...
Page 180: ...178 SERVICE PARTS LIST RAS 6 0HNBRKQ1 RAS 6 5HNBRKQ1 ...
Page 183: ...181 SERVICE PARTS LIST RAS 7 0HNBRMQ1 RAS 8 0HNBRMQ1 ...
Page 184: ...182 SERVICE PARTS LIST RAS 7 0HNBRMQ1 RAS 8 0HNBRMQ1 ...
Page 185: ...183 SERVICE PARTS LIST RAS 10HNBRMQ1 RAS 11HNBRMQ1 RAS 12HNBRMQ1 ...
Page 186: ...184 SERVICE PARTS LIST RAS 10HNBRMQ1 RAS 11HNBRMQ1 RAS 12HNBRMQ1 ...
Page 187: ...HS2019266A ...