![Hitachi Set Free mini-HNRQ1 Series Service Manual Download Page 51](http://html.mh-extra.com/html/hitachi/set-free-mini-hnrq1-series/set-free-mini-hnrq1-series_service-manual_2139434051.webp)
44
1. Initial Troubleshooting
1.1 Checking Electrical Wiring and Power Source
(1) Check the following items for any abnormality in activation of the system.
No.
Check Situation
Check Method
1
Is any power source breaker or fuse
blown?
Check the voltage (Load side) of the breaker and also check the continuity of the fuse
with a tester.
2
Is voltage at the secondary side of the
transformer correct?
Disconnect at the secondary side of the transformer and measure voltage with a tester.
3
Is wiring firmly secured and
correctly connected?
Check that the following wiring connection on O.U./I.U. printed circuit
boards (PCBs) is not loose:
●
The connection for thermistors
●
The connection for the wired controller cable
●
The connection for communication cable
●
Each connection for power source line
Check that the wiring connection on O.U./I.U. PCBs is not loose or misconnected on
the site according to the “Electrical Wiring Diagram”.
Notes:
●
If the fuse(s) on an I.U. PCB blows out, diagnose the cause of over current and recover the fuse(s).
●
In addition, check the power source of optional parts because the fuse may blow out because of the power source failure.
(2) Electrical Characteristics
Model
Power Supply
Voltage Range
Start current
Rated Current Input
MOP
MCA
Voltage
PH
Hz
Max
Min
Cooling
Heating
(V)
Φ
Hz
(V)
(V)
A
A
A
A
A
RAS-3.0HNBRKQ1
220~240
1
50
264.0
198
8.7
9.5
9.9
32
21
RAS-3.5HNBRKQ1
220~240
1
50
264.0
198
8.7
12.9
12.3
32
21
RAS-4.0HNBRKQ1
220~240
1
50
264.0
198
10.6
12.6
14.0
40
31
RAS-4.5HNBRKQ1
220~240
1
50
264.0
198
10.6
14.8
16.1
40
31
RAS-5.0HNBRKQ1
220~240
1
50
264.0
198
10.6
18.3
19.2
40
31
RAS-6.0HNBRKQ1
220~240
1
50
264.0
198
10.6
20.2
20.7
40
31
RAS-6.5HNBRKQ1
220~240
1
50
264.0
198
10.6
26.0
24.0
40
31
RAS-7.0HNBRMQ1
380~415
3
50
456.5
342
8.5
13.0
12.0
25
20
RAS-8.0HNBRMQ1
380~415
3
50
456.5
342
8.5
14.0
13.0
25
20
RAS-10HNBRMQ1
380~415
3
50
456.5
342
20.0
19.0
18.0
40
28
RAS-11HNBRMQ1
380~415
3
50
456.5
342
20.0
20.0
19.0
40
28
RAS-12HNBRMQ1
380~415
3
50
456.5
342
20.0
21.0
20.0
40
28
MCA: Minimum Circuit Ampacity (A);
MOP: Maximum Overcurrent Protective Device (A)
Notes:
●
Power voltage ranges are the following.
Supply Voltage: Rated Voltage within ±10%; Starting Voltage: Rated Voltage within -15%;
Operating Voltage: Rated Voltage within ±10%.
●
Do not connect the ground wiring to gas piping, water piping, or a lightning conductor.
Gas Piping: An explosion and ignition may occur if gas is escaping.
Water Piping: There is no effective electrical ground provided when hard vinyl piping is used.
Lightning Conductor: The electrical potential of the earth increases when a lightning conductor is used.
TROUBLESHOOTING
Summary of Contents for Set Free mini-HNRQ1 Series
Page 8: ...1 Installation ...
Page 50: ...43 Troubleshooting ...
Page 60: ...53 d Noise Filter Board NF1 TROUBLESHOOTING ...
Page 123: ...121 Maintenance ...
Page 153: ...External Input Output and Function Setting 151 ...
Page 167: ...Field Work Instructions 165 ...
Page 172: ...Service Parts List 170 ...
Page 175: ...173 SERVICE PARTS LIST RAS 3 0HNBRKQ1 RAS 3 5HNBRKQ1 ...
Page 176: ...174 SERVICE PARTS LIST RAS 3 0HNBRKQ1 RAS 3 5HNBRKQ1 ...
Page 177: ...175 SERVICE PARTS LIST RAS 4 0HNBRKQ1 RAS 4 5HNBRKQ1 RAS 5 0HNBRKQ1 ...
Page 178: ...176 SERVICE PARTS LIST RAS 4 0HNBRKQ1 RAS 4 5HNBRKQ1 RAS 5 0HNBRKQ1 ...
Page 179: ...177 SERVICE PARTS LIST RAS 6 0HNBRKQ1 RAS 6 5HNBRKQ1 ...
Page 180: ...178 SERVICE PARTS LIST RAS 6 0HNBRKQ1 RAS 6 5HNBRKQ1 ...
Page 183: ...181 SERVICE PARTS LIST RAS 7 0HNBRMQ1 RAS 8 0HNBRMQ1 ...
Page 184: ...182 SERVICE PARTS LIST RAS 7 0HNBRMQ1 RAS 8 0HNBRMQ1 ...
Page 185: ...183 SERVICE PARTS LIST RAS 10HNBRMQ1 RAS 11HNBRMQ1 RAS 12HNBRMQ1 ...
Page 186: ...184 SERVICE PARTS LIST RAS 10HNBRMQ1 RAS 11HNBRMQ1 RAS 12HNBRMQ1 ...
Page 187: ...HS2019266A ...